16.5.20 PCB Communication Error (H74)
Malfunction Decision Conditions:
When External PCB connection is select "YES" and no communication with External PCB micon for 10 seconds
and above.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty indoor PCB.
3
Faulty indoor sub PCB.
Abnormality Judgment:
After 1 minute operation started.
PCB communication error
H74 happens check connection at CN-PWR normal?
Check CN-PWR 230/240 V?
Check CN-COMM situation on terminal 1 & 2 and 3 & 1
Replace indoor PCB
YES
YES
YES
184
For safety reason and to prevent
component breakdown, always switch
Caution
off the power before remove and
connect the component.
NO
Correct connection at CN-PWR
NO
Abnormal AC POWER supply
NO
Replace sub PCB