LG ARUB80LT2 Installation Manual page 76

Multi v sync ii type arub series outdoor unit
Hide thumbs Also See for ARUB80LT2:
Table of Contents

Advertisement

Test Run
Refrigerant Checking Function
1. This function charges appropriate amount of refrigerant automatically through cycle operation.
2. This function judges refrigerant leakage and overcharging.
3. It can be used with refrigerant auto charging function.
Main
PCB
Wait for 3 min. after power reset
SW01S
Main
PCB
Set the Dip S/W.
SW01B
Refrigerant Checking : 1,2,7,14 ON
SW02B
Main
Press the black button on main PCB.
PCB
( Press until '608' is displayed )
SW01V
Main
Press the black button on main PCB
PCB
SW01V
IDU runs with cooling mode in order.
Excess of
Refrigerant
IDU, ODU are turned off
Main
Press the black button on main PCB
PCB
SW01V
Press the black button for 2 sec. after
turning off all of dip S/W.
76
Outdoor Unit
Start
Judging
Refrigerant
Amount
Scarcity of
Impossible
Refrigerant
To Judge
Completed
Note
1. In case air temperature is out of guaranteed
temperature, refrigerant checking function may end
without performing refrigerant checking. Use
guaranteed temperature range only.
2. During the process of judging refrigerant amount, if
the cycle isn't stable, refrigerant checking function
may end without performing refrigerant checking.
Note 1)
Note

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents