Operating temperatures:
DHW storage
tank temp (upper sensor)
DHW storage tank
temp (lower sensor)
DHW flow temp
DHW circulation temp
Common flow temp
System flow temp
Outside temp
HC2, flow temp
HC3, flow temp
Readable setpoints:
Cascade temp. setpoint
System temp. setpoint
Heat pump information
Heat pump flow temp
Heat pump return temp
Source circuit in
Source circuit out
Hot gas
Evaporator pressure
Condenser pressure
Source pump status
Source restriction valve /
Source pump speed
Suction gas temp
Condenser temperature
difference
Temp diff evaporator
Supply pump speed
Supply pump status
Request
Current capacity
Additional heat source
information:
Additional heat source
status
Patruunapolku 5, FI-79100 LEPPÄVIRTA | Tel. +358 20 1230 800 | www.gebwell.com | info@gebwell.fi
CLIMATIX MODBUSREGISTERS
Read/
Register
ID
Write
type 1)
B2
R
3x
B3
R
3x
B38
R
3X
B39
R
3X
B10
R
3x
B11
R
3x
B9
R
3x
B12
R
3x
B14
R
3x
B10
R
3x
B11
R
3x
B21
R
3x
B71
R
3x
B91
R
3x
B92
R
3x
B81
R
3x
H82
R
3x
H83
R
3x
Q8
R
3x
Y8 /
R
3x
Q8
B85
R
3x
R
3x
R
3x
Q9
R
3x
Q9
R
3x
R
3x
R
3x
K27
R
3x
Business ID: FI20089567 | Domicile Leppävirta
8.6.2021
Register
Unit
address
701
°C
702
°C
-
°C
-
°C
901
°C
805
°C
101
°C
604
°C
1004
°C
902
°C
815
°C
201
°C
202
°C
301
°C
302
°C
303
°C
304
bar
305
bar
309
0=Off / 1=On
306
%
307
°C
203
°C
308
°C
204
%
205
0=Off / 1=On
213
%
214
%
806
0=Off / 1=On
Gebwell Ltd.
Devices 2,
Resolution
Device 1
(divider) 2)
(master)
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
10
x
x
1
x
10
x
10
x
10
x
1
x
x
1
x
1
x
x
1/7
3 etc.
(slave)
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Advertisement

Table of Contents
loading

Table of Contents