Mitsubishi Electric City Multi PLFY Series Technical & Service Manual page 12

Hide thumbs Also See for City Multi PLFY Series:
Table of Contents

Advertisement

3-2. ELECTRICAL PARTS SPECIFICATIONS
Service ref.
Symbol PLFY-WL10VFM-E.TH
Parts name
Thermistor
(Room temperature
TH21
detection)
Thermistor
(Pipe temperature
TH22
detection/inlet)
Thermistor
(Pipe temperature
TH23
detection/outlet)
Fuse
FUSE
(Indoor controller board)
Fan motor
MF
Vane motor
MV
Drain pump
DP
Drain float switch
FS
Power supply
TB2
terminal block
Transmission
TB5
terminal block
MA remote controller
TB15
terminal block
* Refer to WIRING DIAGRAM for the supplied voltage.
3-3. SOUND PRESSURE LEVEL
PLFY-WL·VFM-E
Note: Measured in anechoic room.
OCH717
PLFY-WL15VFM-E.TH
Resistance 0:/15 ", 10:/9.6 ", 20:/6.3 ", 25:/5.4 ", 30:/4.3 ", 40:/3.0 "
Resistance 0:/15 ", 10:/9.6 ", 20:/6.3 ", 25:/5.4 ", 30:/4.3 ", 40:/3.0 "
Resistance 0:/15 ", 10:/9.6 ", 20:/6.3 ", 25:/5.4 ", 30:/4.3 ", 40:/3.0 "
MSBPC20M32 (green label)/MSBPC20M33 (blue label)
Measurement location
PLFY-WL20VFM-E.TH
PLFY-WL25VFM-E.TH
250 V 6.3 A
OUTPUT 50 W
DC12 V 300 "/phase
PMD-12D13ME
INPUT 3 W (DC 13 V) 24R/Hr
Open/short detection
(L, N) Rated to 330 V 30 A*
(M1, M2, S) Rated to 250 V 20 A*
(1, 2) Rated to 250 V 10 A*
Sound pressure level at anechoic room : Low- Mid -High
Service Ref.
PLFY-WL10VFM-E.TH
PLFY-WL15VFM-E.TH
PLFY-WL20VFM-E.TH
PLFY-WL25VFM-E.TH
PLFY-WL32VFM-E.TH
12
PLFY-WL32VFM-E.TH
Sound pressure level dB (A)
25-26-27
25-26-29
27-29-31
27-30-34
27-33-41