Mitsubishi Electric BDT CITY MULTI Installation And Pre-Commissioning Booklet page 16

Table of Contents

Advertisement

R2 SERIES PIPING LIMITATIONS (Continued)
3-2-3. If more than 16 ports are in use, or if there is more than one BC controller in use for one outdoor unit
PURY-P-YLM
Note1. No Header usable on PURY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ;
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ;
Note4. As bends cause pressure loss on transportation of refrigerant, fewer bends design is better ;
Piping length needs to consider the actual length and equivalent length which bends are counted.
Equivalent piping length (m)=Actual piping length+"M" x Number of bends.
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports.
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF).
However, the cooling capacity decreases a little (For details, refer to the chapter OUTDOOR UNITS,
R2 SERIES, 6-4. Correction by port counts of the BC controller).
Note7. Individual indoor units grouped together to connect to the BC controller via one port cannot operate individually
in heating and cooling modes at the same time. I.e., they must all function in either heating or cooling together.
Note8. For sub BC controller CMB-P
P350 unit or less. However, if two sub controllers are used the TOTAL sum of connectable units
connected to BOTH sub controllers must also not exceed that of a P350 unit.
For sub BC controller CMB-P1016V-HB1 the connectable indoor unit capacities may sum to equal that
or a P350 unit or less. However, if two sub controllers are used the TOTAL sum of connectable units
connected to BOTH sub controllers must also not exceed that of a P450 unit.
Note9. Indoor capactiy is described as its model size. For example, PEFY-P63VMA-E, its capacity is P63.
Note10. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.
For example, PEFY-P63VMA-E + PEFY-P32VMA-E : Total Indoor capacity = P63 + P32 = P95.
Note11. To enable the continuous heating mode, set SW4 (848) to ON.
OU
H
H'
Reducer (P15-P50)
(attached with BC controller)
h1
Fig. 3-2-2A Piping scheme
Table
. Piping length limitation
3-2-2-1
Item
Total piping length
Farthest IU from OU
Distance between OU and BC
Farthest IU from BC controller
Heignt between OU and IU (OU above IU)
Heignt between OU and IU (OU under IU)
Height between IU and BC
Height between IU and IU
Heignt between BC(Main or Sub) and BC(Sub) h3
OU : Outdoor Unit ; IU : Indoor Unit ; BC : BC controller
*1. Refer to the section 3-2-7.
*2. Details refer to Fig.3-2-2-1
*3. Farthest Indoor from BC controller "B+d or C+D+e or C+E+f " can exceed 40m till 60m if no Indoor sized P200, P250 connected.
Details refer to Fig.3-2-2-1
*4. Distance of Indoor sized P200, P250 from BC must be less than 10m, if any.
*5. When using 2 Sub BC controllers, max. height "h3" should be considered.
*6. 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
*7. 60m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
Fig. 3-2-2-1 Piping length and height between IU and BC controller
70
60
50
40
30
20
10
0
0
Height difference between the main BC controller
16
V-GB1 the connectable indoor unit capacities may sum to equal that of a
A
BC controller (Main BC)
CMY-Y102SS-G
(Joint)
a
b
CMY-R160-J1
(Joint)
IU
IU
(P15-P80)
(P100-P250)
Piping in the figure
A+B+C+D+E+a+b+c+d+e+f
A+C+E+f
A
B+d or C+D+e or C+E+f
H
H'
h1
h2
5
10
15
and indoor unit (m)
CMY-R160-J1
(Liquid side)
M
S
CMY-R160-J1
(Gas side)
Fig. 3-2-2AA
CMY-Y202S-G2
CMY-Y102LS-G2
CMY-Y102SS-G2
BC controller (Sub BC)
D
(Joint)
C
E
BC controller (Sub BC)
B
d
c
IU
IU
Max.3 sets for 1 port.
Total capacity < = P80
OU : Outdoor unit, IU : Indoor unit
(m [ft.])
Max. length
Max. equivalent length
*1
-
165 [541']
190 [623']
110 [360'] *1
110 [360'] *1
40 [131'] *2*3
40 [131'] *2*3
50 [164'] *6
-
40 [131'] *7
-
15 [49'] (10 [32']) *4
-
15 [49'] (10 [32']) *4
-
15 [49'] (10 [32']) *5
-
Table3-2-2-3. Piping "A"size selection rule
Outdoor Model
Pipe(High pressure)
P200YLM
ø15.88 [5/8"]
P250YLM
ø19.05 [3/4"]
P300YLM
ø19.05 [3/4"]
P350YLM
ø19.05 [3/4"]
Table3-2-2-4. Piping "B" size seleciton rule
Total down-stream Indoor capacity
Pipe(Liquid)
P
1
4
0
r o
e l
s s
ø
Table3-2-2-5
. Piping "C", "D", "E" size selection rule
Total down-stream Indoor capacity
Pipe(Lequid)
P200 or less
ø9.52 [3/8"]
P201 to P300
ø9.52 [3/8"]
P301 to P350
ø12.70 [1/2"]
P351 to P400
ø12.70 [1/2"]
P401 to P450
ø15.88 [5/8"]
HP : High pressure, LP:Low pressure
Table3-2-2-6
. Piping "a", "b", "c", "d", "e", "f" saize selection rule (mm [in.])
Indoor Unit size
Pipe(Lequid)
P15 to P50, GUF-50RD(H)
ø6.35 [1/4"]
P63 to P140, GUF-100RD(H)
ø9.52 [3/8"]
P200
ø9.52 [3/8"]
P250
ø9.52 [3/8"]
Joint CMY-R160-J1 Liquid side
226
(M)ø3/8"(Brazing)
BC controller
(M)ø3/8"(Brazing)
Joint CMY-R160-J1 Gas side
N
226
T
(S)ø5/8"(Brazing)
IU
(S)ø5/8"(Brazing)
IU
e
h1
h3
h2
f
h1
IU
Table3-2-2-2. Bent equivalent length "M"
Outdoor Model
M (m/bent [ft./bent])
P200YLM
0.35 [1.15']
P250YLM
0.42 [1.38']
P300YLM
0.42 [1.38']
P350YLM
0.47 [1.54']
(mm [in.])
Pipe(Low pressure)
ø19.05 [3/4"]
ø22.20 [7/8"]
ø22.20 [7/8"]
ø28.58 [1-1/8"]
(mm [in.])
Pipe(Gas)
9
5 .
2
3 [
8 /
] "
ø
1
5
8 .
8
5 [
8 /
] "
(mm [in.])
Pipe(HP Gas)
Pipe(LP Gas)
ø15.88 [5/8"]
ø19.05 [3/4"]
ø19.05 [3/4"]
ø22.20 [7/8"]
ø19.05 [3/4"]
ø28.58 [1-1/8"]
ø22.20 [7/8"]
ø28.58 [1-1/8"]
ø22.20 [7/8"]
ø28.58 [1-1/8"]
Pipe(Gas)
ø12.70 [1/2"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.20 [7/8"]
(N)ø9.52ID
(T)ø19.05ID

Advertisement

Table of Contents
loading

This manual is also suitable for:

P200P250Ep200Ep250P300P350 ... Show all

Table of Contents