1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before installation. Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed. ...
Page 4
WARNING For electrical work, follow the national regulation, legislation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in the electrical work, it will cause electrical shock or fire. Do not use joint cable for indoor/outdoor connection cable.
2. Precaution for Using R32 Refrigerant The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
Page 6
CAUTION 2-5. No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. He/She must not be smoking when carrying out such work.
Page 7
CAUTION Leak detection methods Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. ...
Page 8
CAUTION Labelling Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery ...
3. Specifications Indoor CS-PZ25TKE CS-PZ35TKE Model Outdoor CU-PZ25TKE CU-PZ35TKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 2.50 3.00 0.85 3.40 3.90 Capacity BTU/h 2900 8530 10200 2900...
Page 10
Indoor CS-PZ25TKE CS-PZ35TKE Model Outdoor CU-PZ25TKE CU-PZ35TKE Type Hermetic Motor / Rotary Hermetic Motor / Rotary Compressor Motor Type Brushless (6-poles) Brushless (6-poles) Output Power Type Cross-Flow Fan Cross-Flow Fan Material ASG20K1 ASG20K1 Motor Type DC / Transistor (8 poles)
Page 11
Indoor CS-PZ25TKE CS-PZ35TKE Model Outdoor CU-PZ25TKE CU-PZ35TKE Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8) Standard length m (ft) 5.0 (16.4) 5.0 (16.4) Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2) 3 (9.8) ~ 15 (49.2)
Page 12
Indoor CS-PZ50TKE Model Outdoor CU-PZ50TKE Performance Test Condition EUROVENT Phase, Hz Single, 50 Power Supply Min. Mid. Max. 0.98 5.00 5.40 Capacity BTU/h 3340 17100 18400 kcal/h 4300 4640 Running Current – 7.50 – Input Power 1.68k 1.89k Annual Consumption –...
Page 13
Indoor CS-PZ50TKE Model Outdoor CU-PZ50TKE Type Hermetic Motor / Rotary Compressor Motor Type Brushless (4-poles) Output Power Type Cross-Flow Fan Material ASG20K1 Motor Type DC / Transistor (8 poles) Input Power 47.3 Output Power Cool Heat Cool Heat 1030 Cool 1090 Speed Heat...
Page 14
Indoor CS-PZ50TKE Model Outdoor CU-PZ50TKE Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) Standard length m (ft) 5.0 (16.4) Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2) I/D & O/D Height different m (ft) 15.0 (49.2) Additional Gas Amount...
Page 15
Indoor CS-UZ60TKE Model Outdoor CU-UZ60TKE Performance Test Condition EUROVENT Phase, Hz Single, 50 Power Supply Min. Mid. Max. 0.98 6.25 7.10 Capacity BTU/h 3340 21300 24200 kcal/h 5380 6110 Running Current – 8.60 – Input Power 1.93k 2.40k Annual Consumption –...
Page 16
Indoor CS-UZ60TKE Model Outdoor CU-UZ60TKE Type Hermetic Motor / Rotary Compressor Motor Type Brushless (4-poles) Output Power Type Cross-Flow Fan Material ASG20K1 Motor Type DC / Transistor (8 poles) Input Power 94.8 Output Power Cool Heat Cool 1030 Heat 1040 Cool 1170 Speed...
Page 17
Indoor CS-UZ60TKE Model Outdoor CU-UZ60TKE Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) Standard length m (ft) 5.0 (16.4) Length range (min – max) m (ft) 3 (9.8) ~ 30 (98.4) I/D & O/D Height different m (ft) 15.0 (49.2) Additional Gas Amount...
4. Features Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control Environment Protection Non-ozone depletion substances refrigerant (R32) Long Installation Piping Long piping up to 15 meters Easy to use remote control ...
Remote Control • Manually adjustable. Air Filters receiver Air Purifying Filter (CS-UZ60TKEW) Outdoor Unit Remote Control 5.3.1 CS-PZ25TKE CS-PZ35TKE CS-PZ50TKE Remote control display OFF/ON Powerful/Quiet operation Fan speed selection FAN SPEED Airflow direction selection Operation mode Temperature setting...
Page 20
5.3.2 CS-UZ60TKE Remote control display OFF/ON Powerful/Quiet operation Fan speed selection FAN SPEED Operation mode Airflow direction selection Sleep mode operation Temperature setting Timer setting Clock setting Check...
6. Dimensions Indoor Unit & Remote Control 6.1.1 CS-PZ25TKE CS-PZ35TKE <Top View> <Side View> <Side View> Air intake <Front View> direction Air outlet Right direction piping Left hole piping hole <Bottom View> <Remote Control> FAN SPEED <Rear View> 41-61 <Remote Control Holder>...
Page 22
6.1.2 CS-PZ50TKE <Top View> <Side View> <Side View> Air intake <Front View> direction Air outlet Right Left direction piping piping hole hole <Bottom View> <Remote Control transmitter> FAN SPEED <Back View> Gas side Liquid side <Remote Control Holder> 41-61 Relative position between the indoor unit and the installation plate <Front View> 496.6 16.4 Installation...
Page 23
6.1.3 CS-UZ60TKE <Top View> <Side View> <Side View> Air intake <Front View> direction 1070 Right Air outlet piping Left direction hole piping hole <Bottom View> <Remote Control transmitter> FAN SPEED <Back View> Gas side Liquid side <Remote Control Holder> 41-61 Relative position between the indoor unit and the installation plate <Front View>...
Outdoor Unit 6.2.1 CU-PZ25TKE CU-PZ35TKE <Top View> 67.6 (104.7) 570.3 104.9 60.5 Space necessary for installation 100 mm 100 mm 1000 mm Anchor Bolt Pitch 320 × 570 <Side View> <Side View> <Front View> 3-way valve at Gas side Unit : mm (Low Pressure) 2-way valve at Liquid side (High Pressure)
Page 25
6.2.2 CU-PZ50TKE <Top View> Space necessary for installation 100mm 100mm 1000mm Anchor Bolt Pitch 330 × 540 <Side View> <Side View> <Front View> 3-way valve at Gas side 2-way valve at Liquid side Unit : mm (Low Pressure) (High Pressure)
Page 26
6.2.3 CU-UZ60TKE <Top View> Space necessary for installation 34.7 (131) 100 mm 100 mm 1000 mm Anchor Bolt Pitch 330 × 540 <Side View> <Side View> <Front View> Unit : mm 3-way valve at Gas side (Low Pressure) 2-way valve at Liquid side (High Pressure)
12. Installation Instruction 12.1 Select the Best Location 12.1.1 Indoor Unit 12.1.3 Indoor/Outdoor Unit Installation Diagram Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. There should not be any heat source or steam r i d o i t o i t...
12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Ceiling Wall Wall More than More than Indoor unit More than 2 screw Installation plate 266 mm 266 mm For best strength of PIPE...
Page 52
Mount the installation plate on the wall with 5 screws or more (at least 5 screws). (If mounting the unit on the concrete wall, consider using anchor bolts.) Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
Page 53
12.2.3 Indoor Unit Installation • Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. • Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Shock absorber...
Page 54
Exchange the drain hose and cap Rear view for left piping installation Connection cable Piping Drain hose More than 950 mm (1.0 ~ 2.0HP) or Connection cable Drain hose 1150 mm (2.25HP) Drain cap Adjust the piping slightly Drain hose downwards.
Page 55
Terminal Board Control Board Earth Wire longer Earth Wire than longer than Recommended others others AC length (mm) 55 35 35 50 40 35 60 AC wires wires for for safety safety reason reason Recommended length (mm) Holder Holder Power supply Indoor &...
12.3 Outdoor Unit 12.3.1 Install the Outdoor Unit After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt, screws or nails.
Page 57
AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM 12.3.3 Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. There is no extra refrigerant in the outdoor unit for air purging.
Page 58
12.3.4 Connect the Cable to the Outdoor Unit Remove the control board cover from the unit Terminal Board by loosening the screw. Connection cable between indoor unit and Earth wire outdoor unit shall be approved longer than others polychloroprene sheathed 4 × 1.5 mm AC wires (1.0 ~ 1.5HP) or 4 ×...
Page 59
12.3.7 How to Take Out Front Grille Please follow the steps below to take out front grille if necessary such as when servicing. Set the vertical airflow direction louvers to the horizontal position. Slide down the 2 caps (1.0 ~ 2.0HP) or 3 caps (2.25HP) on the front grille as shown in the illustration at right, and then remove the 2 (1.0 ~ 2.0HP) or 4 (2.25HP) mounting screws.
Page 60
12.3.10 Check the Drainage Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) Pour a glass of water into the drain tray-styrofoam. Ensure that water flows out from drain hose of the indoor unit. Drain tray-styrofoam 12.3.11 Evaluation of the Performance ...
13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
Page 62
2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
Page 64
3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
Page 65
7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
Page 66
11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
Page 70
13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
Page 71
13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
Page 72
13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
Page 74
2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
Page 75
13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
Page 76
13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number applications Solidus Liquidus Kgf•cm temp material Liquidity is good at low temperature, 49.0 14.5...
Page 77
13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
Page 78
(Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
Page 80
1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
14. Operation Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Manual Fan Speed [Cooling, Dry] Fan motor’s number of rotation is determined according to remote control setting. Remote control ○ ○ ○ ○ ○ CS-PZ25TKE CS-PZ35TKE Remote control ○ ○ ○ ○ ○ CS-PZ50TKE CS-UZ60TKE [Heating] Fan motor’s number of rotation is determined according to remote control setting.
ii Auto Fan Speed [Cooling, Dry] According to room temperature and setting temperature, indoor fan speed is determined automatically. When set temperature is not achieved, the indoor fan will operate according to pattern below. When set temperature achieved, the indoor fan speed will be fixed. When thermostat off, the fan stop periodically. [Heating] ...
Page 84
Usual 17.5 32.5 Manual Control with dew 17.5 32.5 Heating Manual Usual 21.2 32.5 43.8 CS-PZ25TKE CS-PZ35TKE Vane Angle (°) Operation Mode Usual (Ventilation) 5 ~ 35 Auto Control with dew 5 ~ 35 Cooling Usual (Ventilation) 12.5 27.5 Manual Control with dew 12.5...
14.4.2 Horizontal Airflow (For UZ60TKE only) Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as stated below. It does not swing during fan motor stop. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.
14.6 Random Auto Restart Control When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.
14.9 Quiet Operation (Heating) A. Purpose To provide quiet heating operation compare to normal operation. B. Control condition a. Quiet operation start condition When “POWERFUL/QUIET” button at remote control is pressed. b. Quiet operation stop condition When one of the following conditions is satisfied, quiet operation stops: a.
15. Protection Control 15.1 Protection Control for All Operations 15.1.1 Restart Control (Time Delay Safety Control) The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
Page 89
15.1.4 Compressor Overheating Prevention Control Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below. If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking.
15.2 Protection Control for Cooling & Soft Dry Operation 15.2.1 Outdoor Air Temperature Control The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. ...
15.2.6 Odor Cut Control To reduce the odor released from the unit. Start Condition AUTO FAN Speed is selected during COOL or DRY operation. During freeze prevention control and timer preliminary operation, this control is not applicable. Control content ...
Page 92
15.3.6 Deice Operation When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan motor stop and operation LED blinks. 15.3.7 Low Pressure Protection Control During low ambient heating operation (below -15°C), if the pipe temperature drops below -16°C, the max frequency will be reduced and limited.
16. Servicing Mode 16.1 Auto OFF/ON Button AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds.
REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
16.2.2 Operation mode during Heating only Operation The table below shows the operation mode comparison when Heating Only Operation Mode Activated and Deactivated. Operation Mode Heating Only Operation Mode Activated Heating Only Operation Mode Deactivated After 30s sampling, the unit will judge the operation After 30s sampling, regardless of the indoor intake or mode base on remote controller temperature setting and AUTO...
Page 96
16.3.3 RESET (AC) To restore the unit’s setting to factory default. Press once to restore the unit’s setting. 16.3.4 TIMER ▲ To change indoor unit indicator’s LED intensity. Press continuously for 5 seconds. 16.3.5 TIMER ▼ To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F). Press continuously for 10 seconds.
Page 97
To enter zone 2 area: (Press continuosly for T ≥ 5 secs) Once T ≥ 5secs Normal display Enter Zone1 Enter Zone2 mode [range (50~99)] Function & Options list: Note: The functions described in the table may not be applicable to the model and may subject to change without further notice.
17. Troubleshooting Guide 17.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table on the right.
17.2 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
17.3 Breakdown Self Diagnosis Function 17.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) Every press of the button (up or down) will Once abnormality has occurred during operation, increase abnormality numbers and transmit the unit will stop its operation, and Timer LEDs abnormality code signal to the main unit.
17.4 Error Codes Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only Indoor/outdoor wire terminal Indoor/outdoor Indoor/outdoor operation can After operation for abnormal start by entering communication not...
Page 102
Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality Expansion valve and lead wire and connector ...
17.5 Self-diagnosis Method 17.5.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused Faulty indoor unit PCB.
Page 104
17.5.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. ...
Page 105
17.5.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 106
17.5.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor.
Page 107
17.5.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused Lack of gas Broken CT (current transformer) ...
Page 108
17.5.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused ...
Page 109
17.5.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 110
17.5.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 111
17.5.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 112
17.5.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 113
17.5.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 114
17.5.12 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective.
Page 115
17.5.13 H34 (Outdoor Heat Sink Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 116
17.5.14 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 117
17.5.15 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 118
17.5.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. ...
Page 119
17.5.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
Page 120
17.5.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) Malfunction Caused ...
Page 121
17.5.19 F11 (4-way valve Abnormality) Malfunction Decision Conditions When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
Page 122
17.5.20 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor pipe temperature is below -1.0°C. Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).
Page 123
17.5.21 F90 (Power Factor Correction Protection) Malfunction Decision Conditions To maintain DC voltage level supply to power transistor. To detect high DC voltage level after rectification. Malfunction Caused During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
Page 124
17.5.22 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused Lack of gas. 3-way valve close. Troubleshooting...
Page 125
17.5.23 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect Faulty Outdoor PCB Faulty compressor Troubleshooting...
Page 126
17.5.24 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
Page 127
17.5.25 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (120°C) is detected by the IPM temperature sensor. Multi Models Only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
Page 128
17.5.26 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor. Malfunction Caused Faulty compressor tank temperature sensor 2/3 way valve closed ...
Page 129
17.5.27 F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
Page 130
17.5.28 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused DC current peak due to compressor failure. ...
High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.1 CS-PZ25TKE CS-PZ35TKE 18.1.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 18.1.1.1...
Page 132
Pull out the main Detach connector as labeled from the electronic controller electronic controller, then pull out the halfway. main controller gently. G301 AC304 AC303 Detach the Earth wire screw. RY-PWR CN-FM Detach the CN-DISP connector then remove the indicator PCB complete. Remove the screw to dismantle CN-STM1 the terminal board complete.
Page 133
18.1.1.4 To Remove Control Board 12. Remove 4 screws holding the control board together then pull out the control board. Figure 6 18.1.1.5 To Remove Cross Flow Fan and Indoor Fan Motor Remove stepping motor lead wire connectors. Pull out to remove the drain hose from the Discharge Grille.
Page 134
Remove the screw that holds the cross flow fan and the fan motor shaft. Figure 8 Remove the bearing by pulling it out gently. Remove the screw from the evaporator. Figure 9...
Page 135
19. Push the holdfast to the left and lift up the evaporator. Evaporator 20. Remove the cross flow fan from 21. Fan motor can be removed after the the unit by pulling it to the left and removal of cross flow fan. downward.
WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.2 CS-PZ50TKE 18.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 18.2.1.1 To Remove Front Grille...
Page 137
Pull out the main Detach connectors as labeled from the electronic controller electronic controller. Then pull out main halfway. controller gently. AC304 AC303 G301 Detach the earth wire connection. RY-PWR Remove screw Terminal Board complete and earth wire. CN-FM Detach the CN-DISP CN-CNT connector then remove the indicator complete.
Page 138
18.2.1.4 To Remove Control Board 12. Remove 4 screws holding the control board and then pull out the control board. Figure 6 18.2.1.5 To Remove Cross Flow Fan and Indoor Fan Motor Remove the screw that holding the cross flow fan and fan motor shaft. Figure 7...
Page 139
Remove the bearing by pulling it out gently. Remove the screw from the evaporator. Figure 8 16. Push the holdfast to the left and lift up the evaporator. Evaporator 17. Remove the cross flow fan from 18. Fan motor can be removed after the the unit by pulling it to the left and removal of cross flow fan.
Page 140
Cross Flow Fan Reminder: To reinstall the cross flow fan, ensure cross flow fan is in line as shown in figure 10. Figure 10...
WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.3 CS-UZ60TKE 18.3.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 18.3.1.1 To Remove Front Grille...
18.4 Outdoor Electronic Controller Removal Procedure 18.4.1 CU-PZ25TKE CU-PZ35TKE Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
Page 146
18.4.2 CU-PZ50TKE Caution! When handling electronic controller, be careful of electrostatic discharge. 1. Remove the 5 screws of the Top Panel. 5. Remove the Control Board as follows: Fig. 1 2. Remove the 8 screws of the Front Panel. Fig. 4 Fig.
Page 147
18.4.3 CU-UZ60TKE Caution! When handling electronic controller, be careful of electrostatic discharge. 1. Remove the 5 screws of the Top Panel. 5. Remove 2 screws for the plate of Terminal Board Cover. Fig. 1 Fig. 4 6. Remove the Control Board. 2.
20. Service Data Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced heating mode. 20.1 Cool Mode Outdoor Air Temperature Characteristic Room Temperature: 27/19°C, Cooling Characteristic Fan: High Pipe Length: 5.0m Freq: Rated Fc 20.1.1 CS-PZ25TKE CU-PZ25TKE...
20.2 Heat Mode Outdoor Air Temperature Characteristic Room Temperature: 20°C, Heating Characteristic Fan: High Pipe Length: 5.0m Freq: Rated Fh 20.2.1 CS-PZ25TKE CU-PZ25TKE Outdoor Air Temperature ( 4.50 4.00 3.50 3.00 2.50 2.00 1.50 Outdoor Air Temperature ( 3.50 3.00 2.50 2.00 1.50...
Page 156
20.2.2 CS-PZ35TKE CU-PZ35TKE Outdoor Air Temperature ( 5.00 4.50 4.00 3.50 3.00 2.50 2.00 Outdoor Air Temperature ( 3.50 3.00 2.50 2.00 1.50 1.00 Outdoor Air Temperature (...
Page 157
20.2.3 CS-PZ50TKE CU-PZ50TKE 65.00 60.00 55.00 50.00 45.00 40.00 35.00 30.00 25.00 -16 -14 -12 -10 Outdoor Air Temperature ( 10.00 9.00 8.00 7.00 6.00 5.00 4.00 3.00 Outdoor Air Temperature ( 5.80 5.30 4.80 4.30 3.80 3.30 2.80 2.30 1.80 -16 -14 -12 -10 Outdoor Air Temperature (...
Page 158
20.2.4 CS-UZ60TKE CU-UZ60TKE 60.00 55.00 50.00 45.00 40.00 35.00 30.00 25.00 -16 -14 -12 -10 Outdoor Air Temperature ( 13.00 12.00 11.00 10.00 9.00 8.00 7.00 6.00 5.00 Outdoor Air Temperature ( 5.00 4.50 4.00 3.50 3.00 2.50 2.00 1.50 -16 -14 -12 -10 Outdoor Air Temperature (...
20.3 Piping Length Correction Factor The characteristic of the unit has to be corrected in accordance with the piping length. 20.3.1 CS-PZ25TKE CU-PZ25TKE CS-PZ35TKE CU-PZ35TKE 1.02 1.00 0.98 0.96 0.94 0.92 Pipe Length (m) 1.04 1.02 1.00 0.98 0.96 0.94 0.92...
Page 160
20.3.2 CS-PZ50TKE CU-PZ50TKE 1.02 0.98 0.94 0.90 Pipe Length (m) 1.05 1.04 1.03 1.02 1.01 1.00 0.99 0.98 0.97 0.96 0.95 Pipe Length (m) Note: The graphs show the factor after added right amount of additional refrigerant.
Page 161
20.3.3 CS-UZ60TKE CU-UZ60TKE 1.03 1.01 0.99 0.97 0.95 2 3 4 5 6 7 8 9 1011121314151617181920212223242526272829303132 Pipe Length (m) 1.01 1.01 1.00 1.00 0.99 0.99 0.98 0.98 0.97 0.97 0.96 2 3 4 5 6 7 8 9 1011121314151617181920212223242526272829303132 Pipe Length (m) Note: The graphs show the factor after added right amount of additional refrigerant.
21. Exploded View and Replacement Parts List 21.1 Indoor Unit 21.1.1 CS-PZ25TKE CS-PZ35TKE CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 163
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-PZ25TKE CS-PZ35TKE REMARK CHASSIS COMPLETE CWD50C1903 ← FAN MOTOR L6CBYYYL0177 ← CROSS-FLOW FAN COMPLETE CWH02C1159 ← BEARING ASSY CWH64K007 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C00770 ← FLARE NUT (LIQUID) CWT251048 ←...
Page 164
21.1.2 CS-PZ50TKE CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 165
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-PZ50TKE REMARK CHASSIS COMPLETE CWD50C1901 FAN MOTOR L6CBYYYL0037 CROSS-FLOW FAN COMPLETE CWH02C1076 BEARING ASSY CWH64K007 SCREW - CROSS-FLOW FAN CWH551146 EVAPORATOR ACXB30C01200 FLARE NUT (LIQUID) CWT251048 FLARE NUT (GAS) CWT251032 CONTROL BOARD CASING CWH102605 TERMINAL BOARD COMPLETE CWA28C2742...
Page 166
21.1.3 CS-UZ60TKE CW H55025 J CW H55051 J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 167
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-UZ60TKE REMARK CHASSIS COMPLETE CWD50C1902 FAN MOTOR L6CBYYYL0176 CROSS-FLOW FAN COMPLETE CWH02C1077 BEARING ASSY CWH64K1010 SCREW - CROSS-FLOW FAN CWH551146 CWD933067 PARTICULAR PIECE EVAPORATOR CWB30C3108 FLARE NUT (LIQUID) CWT251030 FLARE NUT (GAS) CWT251032 CONTROL BOARD CASING CWH102605 PARTICULAR PIECE - TERMINAL...
21.2 Outdoor Unit 21.2.1 CU-PZ25TKE CU-PZ35TKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 169
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-PZ25TKE CU-PZ35TKE REMARK CHASSIS COMPLETE ACXD52K00150 ← FAN MOTOR BRACKET CWD541157 ← SCREW - FAN MOTOR BRACKET CWH551217 ← FAN MOTOR L6CAYYYL0064 ← SCREW - FAN MOTOR MOUNT CWH55252J ← PROPELLER FAN ASSY CWH03K1100 ←...
Page 170
PART NAME & DESCRIPTION QTY. CU-PZ25TKE CU-PZ35TKE REMARK INSTALLATION INSTRUCTION ACXF60-07350 ← INSTALLATION INSTRUCTION ACXF60-07360 ← PANASONIC BADGE CWE373439 ← (Note) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.
Page 171
21.2.2 CU-PZ50TKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 172
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-PZ50TKE REMARK CHASSIS COMPLETE CWD52K1277 FAN MOTOR BRACKET CWD541167 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR ARS6411AC SCREW - FAN MOTOR MOUNT CWH55252J PROPELLER FAN ASSY CWH03K1066 NUT - PROPELLER FAN CWH56053J COMPRESSOR 9RD132XAB21...
Page 173
CU-PZ50TKE REMARK INSTALLATION INSTRUCTION ACXF60-07330 INSTALLATION INSTRUCTION ACXF60-07340 INSTALLATION INSTRUCTION ACXF60-07350 INSTALLATION INSTRUCTION ACXF60-07360 PANASONIC BADGE CWE373439 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.
Page 174
21.2.3 CU-UZ60TKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 175
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-UZ60TKE REMARK CHASSIS COMPLETE ACXD52K00320 FAN MOTOR BRACKET ACXD54-00140 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR L6CAYYYL0076 SCREW - FAN MOTOR MOUNT CWH551106J PROPELLER FAN ASSY ACXH03K00070 NUT - PROPELLER FAN CWH56053J COMPRESSOR 9RD132XAA21...
Page 176
ACXF60-07330 INSTALLATION INSTRUCTION ACXF60-07340 INSTALLATION INSTRUCTION ACXF60-07350 INSTALLATION INSTRUCTION ACXF60-07360 PANASONIC BADGE CWE373439 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock. [PAPAMY] Printed in Malaysia...