LG ARND203DCR4 Installation Manual page 47

Split compact dedicated outdoor air system
Hide thumbs Also See for ARND203DCR4:
Table of Contents

Advertisement

Figure41: UI Module
Drawing
Label Unit Connection
Reference
2
CH1
CH1 port of Other module for communication
DI1
Occupancy
3
DI2
Outside Air filter Switch
DI3
Unassigned
UI1
Unassigned
UI2
Unassigned
UI3
Unassigned
4
UI4
Unassigned
UI5
Space / Return Duct Temperature (Field Option)
UI6
Space / Return Duct Relative Humidity (Field Option)
Figure42: NTC Module
Drawing
Label Unit Connection8
Reference
2
CH1
CH1 port of Other module for communication
RI1
Space / Return Duct Temperature(Field Option)
RI2
Unassigned
RI3
Outdoor Air Temperature
RI4
Leaving Air Temperature(Main Coil) #1
3
RI5
Leaving Air Temperature(Main Coil) #2
RI6
Unassigned
RI7
Supply Air Temperature
RI8
After Heater Air Temperature
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification.
Type
Position Indicates
RS485
NO
(Closed = Occupied)
NO (
Closed = Dirty)
NO (
Closed = Dirty)
0 – 10Vdc
0 – 10Vdc
Sensor Type
Position Indicates
RS485
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
Range
-130-210F
-130-210F
Range
-130-210F
-130-210F
-130-210F
-130-210F
-130-210F
-130-210F
-130-210F
-130-210F