Honeywell C7400 Manual page 19

Solid state economizer system
Table of Contents

Advertisement

Demand Control
Ventilation (DCV)
Outdoor
Below set (DCV
High (Free
LED Off)
Cooling LED Off)
Low (Free
Cooling LED On)
Above set (DCV
High (Free
LED On)
Cooling LED Off)
Low (Free
Cooling LED On)
a
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
b
Power at N terminal determines Occupied/Unoccupied setting:
• W7212: 24 Vac (Occupied), no power (Unoccupied). W7212C returns to minimum position on CO
• W7213,W7214: No power (Occupied), 24 Vac (Unoccupied).
c
Modulation is based on the mixed air sensor signal.
d
Modulation is based on the DCV signal.
e
Modulation is based on the greater of DCV and mixed air sensor signals, between minimum position and either maximum
position (DCV) or fully open (mixed air signal).
f
Modulation is based on the greater of DCV and mixed air sensor signals, between closed and either maximum position (DCV)
or fully open (mixed air signal).
NOTES:
DCV and Free Cooling have setpoints and LED indications.
For models with a B terminal (W7213):
No power to B: cooling mode, free cool enabled. Module follows logic detailed above.
24V power to B: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).
For models with an O terminal (W7214):
24V power to O: cooling mode, free cool enabled. Module follows logic detailed above.
No power to O: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).
SETTINGS AND
ADJUSTMENTS: W7212
CAUTION
Equipment Damage Hazard.
Excessive force can damage potentiometer
controls.
Use a small screwdriver when adjusting enthalpy
changeover and minimum damper position controls.
Table 5. W7212 Economizer I/O Logic.
INPUTS
a
Enthalpy
Return
Y1
Low
On
On
Off
High
On
On
Off
Low
On
On
Off
High
On
On
Off
Compressor
Y2
Stage 1 Stage 2
On
On
On
Minimum position
Off
On
Off
Off
Off
Off
On
On
Off
Modulating
min. position and full-
Off
Off
Off
open)
Off
Off
Off
Minimum position
On
On
On
Modulating
min. position and DCV
Off
On
Off
maximum)
Off
Off
Off
On
On
Off
Modulating
Off
Off
Off
Off
Off
Off
Potentiometers with small screwdriver adjustment slots,
located on device face, provide adjustments for several
parameters (see Fig. 27 for locations on device):
— DCV setpoint.
— Minimum damper position.
— DCV maximum damper position.
— Enthalpy changeover.
— Exhaust setpoint.
19
SOLID STATE ECONOMIZER SYSTEM
OUTPUTS
b
N Terminal
b
Occupied
Unoccupied
Damper
Closed
c
(between
Modulating
closed and full-open)
Closed
d
(between
Modulating
closed and DCV
maximum)
e
Modulating
sensor failure.
2
b
c
(between
d
(between
f
63-2484—03