Screenlok ® Flame Arrestor Cleaning; Rg-Ix - Bradford White RG140T Service Manual

Hide thumbs Also See for RG140T:
Table of Contents

Advertisement

®
ScreenLok
Flame Arrestor Cleaning
Step 1.
Rotate knob of combination thermostat gas valve to the off position.
Step 2.
Remove the outer jacket door.
Step 3.
Remove inner door per Service Procedure RG-I, Steps 3a through 3e.
Step 4. Disconnect the main burner feed line, pilot tube, and
thermocouple/thermopile from combination thermostat gas valve and
remove burner assembly from the combustion chamber.
NOTE: Feedline nut for natural gas control uses right hand threads;
L.P. control uses left hand thread.
Clean ScreenLok
Step 5.
other debris accumulation. Using a soft brush, clear jacket openings of any dirt, dust, restrictions, or
other obstructions.
Remove any debris from burner assembly per Service Procedure RG-V and reinstall burner
Step 6.
assembly into combustion chamber.
Reconnect feedline, thermocouple, and pilot tube to the combination thermostat/gas valve.
Step 7.
Reinstall inner door per Service Procedure RG-I.
Step 8
To resume operation, follow the instructions located on the lighting instruction label or the lighting
Step 9.
instruction located in the Installation and Operation Manual.
®
Flame Arrestor using stiff brush and compressed air to remove any scale or
SERVICE PROCEDURE RG-IX
ScreenLok
39
®
Flame Arrestor Cleaning
39