Download Print this page

Kidde 900-0114 Manual page 2

Combination carbon monoxide & smoke alarm

Advertisement

Combination Carbon Monoxide
& Smoke Alarm
Installation of Smoke Alarm
The combination alarm should be installed to comply with all
local codes having jurisdiction in your area, Article 760 of the
National Electric Code, and NFPA 72. Make certain all alarms are
wired to a single, continuous (non-switched) power line, which is
not protected by a ground fault interrupter. A maximum of
1000 ft. of wire can be used in the interconnect system. Use
standard UL listed household wire (18 gauge or larger as
required by local codes).
FUSE OR CIRCUIT BREAKER
L
N
BLACK
RED
WHITE
First
Alarm
Ordering Information
UPC: 0-47871-00114-9
Part
Number
I 2 of 5
900-0114**
N/A
900-0114-02
200 47871 00114 3
**Not for sale by individual unit
1394 South Third Street, Mebane NC 27302
1-800-880-6788 • www.kiddeus.com
Additional
Alarms
Pack Quantity
Individual
Master Pack (6 units)
Part Number 900-0114
Unit Number KN-COSM-IB
Technical Specifications
Part Number:
900-0114
Unit Number:
KN-COSM-IB
Power Source:
120VAC, 60Hz 25mA max per alarm
9V battery backup
Smoke Sensor:
Ionization
CO Sensor:
Electrochemical
Audio Alarm:
85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range:
5%-95% relative humidity
Size:
5.75" in diameter x 1.7" depth
Weight:
1lb
Wiring:
Quick connect plug with 8" pigtails
Interconnects:
Up to 24 Kidde devices
(of which 18 can be initiating)
Warranty:
5 year limited
5.75"
Dimensions
(w x d x h inches)
Weight
5.8 x 2 x 6.2
1lb
7 x 13 x 7
7.65lbs
Distributed by:
1.7"
Case/
Layers/
Skid
Skid
Skid
Weight
N/A
N/A
N/A
100
5
765lbs
6
1
UNIT
MASTER PACK

Advertisement

loading

This manual is also suitable for:

0-47871-00114-9