Proof Test for 2-Channel H-System Devices
Input value (mA)
20.0
12.0
4.0
23.0
0
Table 5.3
Figure 5.5
Tip
The easiest way to test HiD devices by using a stand-alone HiDTB**-SCT-***-**-**
termination board. In this test, it is not necessary to disconnect the wiring of the existing
application. Faults in a subsequent wiring can be avoided.
Output value
Current source/current sink (mA) for HiD2022(SK)
20.0 ± 0.4
12.0 ± 0.4
4.0 ± 0.4
23.0 ± 0.4
< 0.2
Signal calibration
SL2
4 mA to 20 mA
+ 1
5a
4
5b
- 7
7a
+ 2
1a
5
1b
- 6
3b
Zone 0, 1, 2
Termination Board
Div. 1, 2
Proof test set-up for HiD2022(SK)
HiD2022
SL1
8a
11
+
7a
14
-
10a
12
+
9a
15
-
-
1a, 1b
2a, 2b
+
Multimeter
(mA/V)
I
Multimeter
(mA/V)
II
I
supply
24 V DC
Power
supply
Zone 2
Div. 2
23