Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)*

Planning

3
Planning
3.1

Assumptions

The following assumptions have been made during the FMEDA:
Failure rate based on the Siemens standard SN 29500.
Failure rates are constant, wear is not considered.
External power supply failure rates are not included.
The safety-related device is considered to be of type A device with a hardware
fault tolerance of 0.
The device will be used under average industrial ambient conditions comparable
to the classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar
to IEC/EN 60654-1 Class C with an average temperature over a long period of time
of 40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates
must be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
If you are using the HART function, observe that the HART signal superimposes
an analog signal on the signal line. This is negligible for slow acquisition system
(typically < 25 acquisition/s). If in doubt, use HART filters at the analog input
of the receiving device.
The application program in the programmable logic controller (PLC) is configured
to detect underrange and overrange failures.
Both channels of the 2-channel device can be used in the same safety function.
Observe that both devices use common components and that a simultaneous failure
is possible with a common cause factor of 15 %.
SIL 2 Application
To build a SIL safety loop for the defined SIL, it is assumed as an example that this device
uses 10 % of the available budget for PFD
Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 60 % according to table 2 of IEC/EN 61508-2 for a SIL 2 (sub) system.
SIL 3 Application
SIL 3 can be reached if the two outputs of the device are connected to the same control
interface and evaluated if the deviation remains below 2 %.
To build a SIL safety loop for the defined SIL, it is assumed as an example that this device
uses 10 % of the available budget for PFD
Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 90 % according to table 2 of IEC/EN 61508-2 for a SIL 3 (sub) system.