2-14. E: 53. Drain pump error (Indoor unit)

Wired remote
Indicator
controller
Indoor unit main PCB
Detective actuator
Float switch
Forecast of cause
Check point 1. Check float switch
Check operation of float switch. (any blocking by dust, etc.)
Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
Check point 4. Check voltage of power supply and drain pump
Check drain pump
-> If drain pump is not run on the working condition, check the voltage of the CN71
on the main PCB.
Measurement result
12V: Replace the drain pump
Other than 12V: Replace the main PCB
NOTE: For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-33.
2-14. E: 53. Drain pump error (Indoor unit)
Error code
When Float switch is ON for more than 3 minutes.
"Wiring diagrams"
End
- (03-18) -
E: 53
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
in Chapter 2.
2. Troubleshooting with error code