INSTALLATION AND OPERATION MANUAL,
GAS CABINET BASE CONVECTION STEAMER, GCX-16, GCX-24
5.0 OPERATION INSTRUCTION FOR BOILERS WITH CSD-1 CONTROLS (Continued)
SAFETY LOCKOUT CONDITIONS
High Temperature Condition
A high temperature safety device is installed on the boiler. Should the temperature exceed the
limit of this device, the boiler will be shut down and put in a state of lockout. The "Temperature"
pilot light (red), and the "Standby" pilot (amber), will come on.
High Pressure Condition
A high pressure safety switch is installed on the boiler. Should the pressure exceed the limit of
this device, the boiler will be shut down and put into a state of lockout. The "Pressure" pilot light
(red), and the standby pilot light (amber), will come on. Should this device fail to operate, the
safety relief valve will open.
Low Water Condition
A second low water safety cut off is supplied with the boiler. Should the water level fall below
normal operating levels, this device will shut down and put the boiler in a state of lockout. The
"Low Water" pilot light (red), and the "Standby" pilot light (amber) will come on.
MANUAL 10064R2