Maintenance and Installation

8.1

General Information

Maintenance
8.2

Hard Disk

The VPB 40.1 are maintenance-free. However, some components are subject
to wear and must be replaced.
Include the following measures in the maintenance schedule:
At least once a year, check all plug and terminal connections of the com‐
ponents regarding proper tightness and possible damage. Check that
cables are not broken or crushed. Replace damaged parts immediately.
Check the fan at least once a year.
DANGER
The fan impeller must not to be touched with the hands and must not come into
contact with other objects.
Ensure that the batteries of the VPB 40.1 are fully functional. Activate the
battery test of the UPS program, so that the battery pack is checked during
each restart.
Function compatibility for spare parts is ensured for at least five
years.
The hard disk frame can be accessed by a flap. The hard disk can be replaced,
also including the installation frame.
WARNING
Backup all required application data as well as operating system settings on an
external data carrier!
WARNING
Comply with all ESD protective measures while working with modules and
components! Avoid electrostatic discharges!
NOTICE
Backup the hard disk regularly.
The hard disk to be inserted must already have an installed oper‐
ating system, if no floppy disk drive is connected to the VPB 40.1.
In any case, it is recommended to have a completely installed op‐
erating system on the hard disk, to shorten the installation time!
Bosch Rexroth AG
Maintenance and Installation
Risk of injury by rotating fan impeller!
Data loss due to irregular or missing data back‐
up!
Damages on the VPB 40.1 due to electrostatic
discharges!
Loss of data and resinstallation of the operat‐
ing system and application programs after a
hard disk exchange due to a missing or irreg‐
ular backup.