Viessmann Vitoplus 300 Service Instructions Manual page 83

Wall mounted oil fired condensing boiler for the combustion of low sulphur fuel oil din 51603-el-1 with integral boiler control unit
Table of Contents

Advertisement

Repairs
(cont.)
Extension kit for heating circuit with mixer
Checking the rotational direction of
the mixer motor
1.
Switch ON/OFF switch A at the
extension kit first OFF and then ON
again. The device will carry out the
following self-test:
Mixer "Close" (150 s)
Pump "ON" (10 s)
Mixer "Open" (10 s)
Mixer "Close" (10 s)
Then standard control mode
resumes.
2. Note the rotational direction of the
mixer motor during its self-test.
Then set the mixer manually to
"Open" again.
Note
The flow temperature sensor must
now sense a higher temperature. If
the temperature falls, either the
motor is turning in the wrong direc-
tion or the mixer set is incorrectly
fitted.
Mixer installation instruc-
tions
Changing the rotational direction of
the mixer motor (if required)
1.
Danger
An electric shock can be
life-threatening.
Before opening the equip-
ment, switch OFF the ON/
OFF switch and remove the
mains voltage, for example
by means of the fuse or the
main isolator.
2. Remove the lower and upper hous-
ing cover of the extension kit.
Extension kit installation
instructions
3.
A ON/OFF switch
B Rotational direction switch
Change the rotational direction
switch over:
Troubleshooting
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vp3a

Table of Contents