Viessmann Vitoplus 300 Service Instructions Manual page 80

Wall mounted oil fired condensing boiler for the combustion of low sulphur fuel oil din 51603-el-1 with integral boiler control unit
Table of Contents

Advertisement

Troubleshooting
Repairs
(cont.)
Checking the temperature limiter
80
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 90 °C:
Pull the leads off temperature limiter
A.
Check the continuity of the tempera-
ture limiter with a multimeter.
Remove the faulty temperature lim-
iter.
Install a new temperature limiter.
After commissioning, press reset
button "E" on the control unit.