Start-Up
For Your Safety
A
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
This appliance has a hot surface igniter(s). It is equipped
with an ignition device(s) which automatically lights the
burners. Do not try to light the burners by hand.
BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell near the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
telephone in your building.
Immediately call your gas supplier from a neighbor's
telephone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not turn by
hand, do not try to repair it, call a qualified service
technician. Forced or attempted repair may result in
a fire or explosion.
Do not use this appliance if any part has been under
water, immediately call a qualified service technician
to inspect the appliance and to replace any part of
the control system and any gas control which has
been under water.
Check around unit for debris and remove combustible
products, i.e. gasoline, etc.
ADJUSTMENT SCREW
APPROVED
PROPANE SUPPLY
PRESSURE TEST POINT
MODELS 502CD-2342CD
Figure 4.
FlexGas Gas Pressure Measurement Locations
UNCONTROLLED DOCUMENT IF PRINTED
GAS VALVE
OUTLET TAP
MODELS: 302CD - 902CD
Pre Start-up Check
1. Verify heater is filled with water.
2. Check system piping for leaks. If found, repair
immediately.
3. Vent air from system. Air in system can interfere with
water circulation.
4. Purge air from gas lines up to FlexGas gas train.
Initial Start-up
Tools Needed:
(1) 12-0-12, 24" scale U-tube manometer
(4) 6-0-6, 12" scale U-tube manometers (min.)
(1) Screwdriver
(1) Multi-meter
(1) 3/16" Allen wrench
NOTE: Digital manometers are not recommended.
GAS VALVE
OUTLET TAP
MODELS: 992CD - 2342CD