Configuration
1
>5s
The thermostat must be switched off.
Press the second button from the left for 5 seconds.
The thermostat version appears on the display.
Press OK.
Menu CF01 appears on the display.
Select the required setting with + and -.
Press OK to confirm the setting and move to the next setting.
Turn the selector switch to exit the mode.
Note: The fields with a grey background correspond to the
pre-configured factory settings.
CF01 – Correction of measured temperature
Adjustable from -5 °C to +5 °C.
Example: If the temperature displayed by the appliance is 19 °C
and the temperature measured (by thermometer) is 20 °C, +1 °C
must be set.
CF02 – Displayed temperature in AUTO mode
0
1
8
Set temperature
Measured temperature
2
-5 °C -> +5 °C
4
3