Coding; Dhw"/Group 3 - Viessmann Vitodens 200-W Installation And Service Instructions For Contractors

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Code 2
"Boiler"/Group 2
(cont.)

Coding

Coding in the delivered condition
01:1
Never adjust (only for constant
temperature control units)
04:1
Minimum burner pause time sub-
ject to the boiler load (specified by
boiler coding card)
06:...
Maximum limit of the boiler water
temperature, defaulted in °C by the
boiler coding card
0d:0
Never adjust
0E:0
Never adjust
13:1
Never adjust
14:1
Never adjust
15:1
Never adjust
21:0
No set service interval (hours run)
23:0
No burner service interval
24:0
No "Service" indication on the dis-
play
28:0
No burner interval ignition
2E:0
Never adjust
2F:0
Venting program/fill program disa-
bled
30:1
Internal variable speed circulation
pump (automatic adjustment)
31:...
Set speed of the internal circula-
tion pump when operated as a
boiler circuit pump in %, defaulted
by the boiler coding card
38:0
Status burner control unit: Opera-
tional (no fault)

"DHW"/Group 3

Select "DHW" for weather-compensated control unit
(see page 52).
58
Possible change
04:0
Minimum burner pause time set per-
manently (specified by boiler coding
card)
06:20
Maximum limit of the boiler water
to
temperature within the ranges speci-
06:127
fied by the boiler
21:1
The number of hours run before the
to
burner should be serviced is adjust-
21:100
able from 100 to 10,000 h.
One step
23:1
Interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" indicator is shown on dis-
play (the address is automatically
set and must be manually reset after
a service has been carried out)
28:1
Time interval adjustable from 1 h to
to
24 h. The burner is force-started for
28:24
30 s at a time (only when operating
with LPG).
2F:1
Venting program enabled
2F:2
Fill program enabled
30:0
Internal circulation pump without
variable speed (e.g. temporarily for
service)
31:0
Set speed adjustable from 0 to
to
100 %
31:100
38:≠0
Status burner control unit: Error
Select "3" for constant temperature control unit (see
page 52).