Description Of Functions - Dometic ASCDU15HV 1161 Installation And Operation Manual

Universal self-contained air conditioning unit and q3 control
Hide thumbs Also See for ASCDU15HV 1161:
Table of Contents

Advertisement

Universal Air Conditioning Unit
Function Number
22
23
24
25
26
27
28
29
30
31
32
33
If a factory reset is performed, parameter 19 MUST be set to "CL" and parameter 23 MUST be set to
I
"h1" to enable Aux Heat/Heat mode .

8 .2 Description of Functions

The following sections contain information on the
programmable functions available within the Q3 control.
1: Compressor Time Delay
If programmable function 19 is set to "CL", there will
be a five-minute time delay before the display shows
readings. If an attempt is made to change the five-minute
time delay, the changes will not be recognized by the
system.
2: Fahrenheit, Celsius, or Auto Selection
Select "F" for Fahrenheit. Select "C" for Celsius. Auto
selection defaults to 60 Hz and F.
3: Compressor Restart Differential
The compressor restart differential is the ambient
temperature change needed for the compressor to
cycle on and off. The factory setting of 1.5 °F (0.8 °C)
EN
Description
Fan-Speed Divisions
Aux Heat/Heat
Enable/Disable
Seawater Low Limit
Temp
Humidity Sensor Limit
Air Filter Timing Setting
(x 100 hours)
Select FAMU (Fresh Air
Makeup) Operation
CAN Bus Unit ID
CAN Bus Group ID
Custom Medium Fan
Speeds
Medium Low Fan Speed
Medium Fan Speed
Medium High Fan
Speed
Programmable Functions, Ranges, and Factory Defaults
Factory Default
Required Settings
5
The Q3 control MUST
- -
be set to "h1" for
N/A
N/A
0
N/A
N/A
N/A
2
50
62
74
should be adequate for most applications. Differential
selections are available in increments of 1/8 °. All
program functions must be adjusted in °F, even if
the temperature display is changed from Fahrenheit
to Celsius (refer to "2: Fahrenheit, Celsius, or Auto
Selection" on page 19). To change the settings one
degree, add or subtract eight. Be careful not to set the
compressor restart differential too low. This will cause
the compressor to start and stop often, placing an undue
load on the electrical system and shortening the life of
the compressor.
4: Fan Response Differential
When the fan is in the Auto fan mode, the fan speed
is governed by how much the conditioned space
temperature differs from the set point. The fan runs faster
when the difference is greater. As the conditioned space
cools or warms, and the temperature approaches the set
point, the fan slows down automatically.
Function Range
- - = Aux Heat/Heat
Disabled
h1 = Aux Heat/Heat
this function .
N/A
N/A
1–25 = 100–2500 hours
N/A
N/A
N/A
2 or 5, or 2 or 3
3 = 3 speeds
5 = 5 speeds
Enabled (must be
set to h1)
N/A
N/A
0 = Disabled
N/A
N/A
N/A
2–99
2–99
2–99
19