Checking Sensor Inputs Locally

All temperature sensors connected will have their temperature readings displayed next to the sensor
number on the display.
Checking Status Remotely with a telephone call
1) Call the Guard.
2) Enter your PIN number.
3) From the main menu press 1.
4) You will hear "Enter Sensor Number."
5) Enter the number of the sensor you wish to hear (i.e. 1) or enter 9 to hear the status of the Door
Sensor Input 1 or * to hear the status of Door Sensor Input 2. Note; Door sensors are not
monitored during a power outage.
6) For Temperature Sensor Inputs, you will hear the sensor's temperature and the high and low lim-
its, and how long the sensor has been out of limits in minutes, if it is out of limits.
For Door Sensor Inputs, you will hear the status of the door sensor switches, unless power is out.
7) You will hear the current power status.
Checking Status Remotely with a web browser
1) Open a web browser such as Internet Explorer.
2) Enter the IP address of the device for the URL address. Example; http://192.168.0.73
3) The status of all connected sensors will be displayed.
Consult your IT dept. if you would like the
Java page to be available from outside your network.

Confirming Alarm Conditions Remotely

During callouts, the Guard will prompt you to enter a PIN number, enter either the "Full Access" PIN
or, the "Acknowledge Only" PIN.
If you have received a page or a voice mail message regarding an alarm condition that you wish to
confirm. Simply call the Guard and enter either the "Full Access" PIN or, the "Acknowledge Only"
PIN, the alarm relay will de-energize, and the Guard will stop making callouts for the current alarm
condition. This action does not override the Reminder Call feature.

Confirming Alarm Conditions Locally

To confirm an alarm condition locally push the black button on the top left side of the Guard to see
any alarm conditions. Hold the button for 5 seconds to confirm the alarm condition.
Alarm Conditions must be confirmed individually.
The alarm relay will de-energize, and the Guard will stop making callouts for the current alarm condi-
tion. This action does not override the Reminder Call feature.