Set Temperature Readout Units (°C or °F)
The Guard can display and report temperature readings in degrees Celsius or Fahrenheit. Warning:
Changing the readout units does not automatically change sensor limits.
1) From the Program Menu, press 8
2) You will hear "Degrees is 32, press 1 to change", indicating the temperature reading at freezing
in its current mode. (Default is Fahrenheit)
3) Press 1 to switch to Celsius Temperature Readout, or 2 to return to the Program Menu.
4) You will hear "Degrees is 0."
5) You will be automatically returned to the Program Menu.
Program Power Outage Time Delay
The Guard can delay a programmable amount of time before alarming due to a power outage. The
default time is 5 minutes.
1) From the Program Menu, press 9.
2) You will hear "'Power has been out for, callout time delay is 5 minutes press 1 to change."
3) Press 1 to change, or 2 to return to the Program Menu.
4) You will hear "Enter number followed by the # key."
5) Enter the time delay in minutes (i.e. 15 for 15 minutes or 0 minutes for an immediate callout).
► Acceptable range is 0 to 120 minutes.
6) You will hear the value you just entered.
7) You will be automatically returned to the Program Menu.

Changing the Callout Delay Time

When a refrigerator or freezer's temperature is out of range the Guard will wait this programmable
amount of time before making telephone alert calls. Please note that the total time before a phone
call is made is the Temperature Sensor Time Delay plus the Callout time delay. (Default 2 minutes)
1) From the Program Menu, press *.
2) You will hear "Callout Time Delay is 2 minutes."
3) You will hear "Press 1 to change."
4) Press 1 to change this setting, or 2 to return to the Program Menu.
5) You will hear "Enter number followed by the # key."
6) Enter the time delay in minutes (i.e. 60 for 1 hour).
7) You will hear the value you just entered.
8) You will be automatically returned to the Program Menu.
Application notes can be downloaded from the documentation section of our website at
www.temperatureguard.com.