Charging Non- - Communicating Systems
Charging Procedure:
Force system to operate in high stage
cooling by creating a large differential between room temperature
and set point on thermostat. Use multi- -meter to verify that 24
VAC is present between C, Y1 /Y2 terminals at outdoor unit.
Factory charge amount is shown on unit rating plate for high stage.
Target subcooling chart is provided on back of control box door
see Fig. 18 - - 25 for example. To properly check or adjust charge,
condition must be favorable for subcooling charging. Favorable
conditions exists when outdoor temperature is between 65_F
(18_C) and 100_F (38_C), and the indoor temperature is between
70_F (21_C) and 80_F (27_C). Follow the procedure below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge
by adding or removing 0.6 oz/ft (17.7 g/m) of 3/8 liquid line above
or below 15ft (4.57 m) respectively.
Furnace or Fan Coil Model Number
CNPV*18**
CAP**18**
CNP**24
CNPV*19**
CAP**24
CSPH*24
CSPH*30**
F(E,V)4(A,B,C)NF002
CAP**30
CNP**30
CNP**36
F(E,V)4(A,B,C)N(B,F)003
CAP**36
CNP**42
CAP**42
CSPH*36
CSPH*42**
CNP**31**
CNP**48
CSPH*48**
CNP**37
CNP**43
CAP**48
CNP**60
CSPH*60
F(E,V)4(A,B,C)N(B,F)005
F(E,V)4(A,B,C)NB006
CAP**60
CNP**61
/ = Comb. not allowed
--- = No charge adjust for ID
Note: Charge adders are in decimal format
Table 2 – Required Charge Adjustment for Indoor Coil Model
13
24B
---
/
---
/
---
---
---
/
---
---
---
---
---
/
+0.19
---
---
/
---
/
---
/
---
/
---
/
+.50
/
+.50
/
+.50
/
+.50
/
+.50
/
+.50
/
+.625
/
+.625
/
+.625
/
/
/
/
/
/
/
+.625
/
/
/
/
/
/
/
For standard refrigerant line lengths (80ft/24.4 m or less), allow
system to operate in cooling mode at least 25 minutes. If conditions
are favorable, check system charge by subcooling method. If any
adjustment is necessary, adjust charge slowly and allow system to
operate for 25 minutes to stabilize before declaring a properly
charged system.
If the indoor temperature is below 70°F (21.11°C), or the outdoor
temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) and indoor fan coil /furnace
coil per Table 4. Charge level should then be appropriate for the
system to achieve rated capacity. The charge level should then be
checked at another time when the both indoor and outdoor
temperatures are in a more favorable range.
NOTE: If the line length is beyond 80ft (24.38 m) or greater than
20ft (6.10 m) vertical separation see Long line guideline for special
charging requirement.
Outdoor Model Size
25
36
37
/
/
/
/
/
/
---
/
/
/
/
/
---
/
/
---
/
/
---
/
/
---
---
/
---
/
/
---
/
/
---
---
---
---
---
---
+.50
---
---
+.50
---
+.75
+.50
---
+.75
+.50
---
+.75
+.50
+.75
+.75
+1.25
+.75
+.75
+1.25
+.75
+.75
+1.25
+.75
+1.00
+1.25
+.75
+1.00
+1.25
+.75
+1.00
+.75
+1.00
/
+1.00
/
/
+1.00
/
/
+1.25
+.75
+1.00
+.75
+1.00
/
/
/
/
/
/
/
11
48
49
60
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
---
---
/
---
---
/
---
---
/
---
---
/
---
---
/
---
+0.125
---
---
+0.125
---
---
+0.125
/
+1.5
+.625
+1.00
+1.5
+.625
+1.00
+1.5
+.625
+1.00