4.3.12 - Description of the Alarms menu
This menu is used to display and reset up to 5 active alarms. It
also permits alarm reset. If no alarm is active this menu is not
accessible. See section 6 for a complete description of the
alarm codes and alarm reset.
ALARMS MENU
ITEM #
FORMAT
X ALArM
0 [1]
rESEt ALArM
1 [1]
1 to 55
2 [1]
1 to 55
3 [1]
1 to 55
4 [1]
1 to 55
5 [1]
1 to 55
1
This item is masked when nil
NOTE
*
Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
"time of alarm" "date of alarm" "full CCN alarm message"
- "time of alarm": hh-mm
- "date": dd-mm
- "full CCN alarm message": up to 64 characters
Time and date are displayed if the unit is equipped with an optional CCN/
clock board.
4.3.13 - Description of the Alarms History menu
ALARMS HISTORY MENU
ITEM #
FORMAT
1 [1]
1 to 55
1 to 55
2 [1]
3 [1]
1 to55
4 [1]
1 to 55
5 [1]
1 to 55
6 [1]
1 to 55
7 [1]
1 to 55
8 [1]
1 to 55
9 [1]
1 to 55
10 [1]
1 to 55
1
This item is masked when nil
NOTE
*
Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
"time of alarm" "date of alarm" "full CCN alarm message"
- "time of alarm": hh-mm
- "date": dd-mm
- "full CCN alarm message": up to 64 characters
Time and date are displayed if the unit is equipped with an optional CCN/
clock board.
4.3.14 - Runtime menu description
RUNTIMES 1
[runtiMES 1]
NOTE: The items in brackets show what is displayed on the
user interface.
COMMENTS
X alarms are active
Reset of alarms is requested
To reset all active alarms, continuously press
the Enter key. 'rESET ALArM' is then displayed.
Press the select key again: all alarms are reset.
Current alarm code 1*
Current alarm code 2*
Current alarm code 3*
Current alarm code 4*
Current alarm code 5*
COMMENTS
Alarm history code 1*
Alarm history code 2*
Alarm history code 3*
Alarm history code 4*
Alarm history code 5*
Alarm history code 6*
Alarm history code 7*
Alarm history code 8*
Alarm history code 9*
Alarm history code 10*
RUNTIMES
RUNTIMES 2
MAINTENANCE
[runtiMES 2]
[MAintEnAnCE]
4.3.14.1 - Description of the Runtimes 1 menu
RUNTIMES MENU [2]
ITEM #
FORMAT
UNITS
0
-
-
1
nnnn | M 10 | M100
hrs/10 or 100
2 [1]
nnnn | M 10 | M100
hrs/10 or 100
3 [1]
nnnn | M 10 | M100
hrs/10 or 100
4
nnnn | M 10 | M100
hrs/10 or 100
5 [1]
nnnn | M 10 | M100
hrs/10 or 100
6 [1]
nnnn | M 10 | M100
hrs/10 or 100
7 [1]
nnnn | M 10 | M100
hrs/10 or 100
8
nnnn | M 10 | M100
-/10 or 100
9
nnnn | M 10 | M100
-/10 or 100
10 [1]
nnnn | M 10 | M100
-/10 or 100
11 [1]
nnnn | M 10 | M100
-/10 or 100
12 [1]
nnnn | M 10 | M100
-/10 or 100
13 [1]
nn
hrs/10 or 100
14 [1]
nn
hrs/10 or 100
15 [1]
nn
hrs/10 or 100
16 [1]
nn
hrs/10 or 100
17 [1]
nn
hrs/10 or 100
1
This item is masked when not used
NOTES
*
Certain values are divided by 10 or by 100, so that number of hours or start-
ups of less then 10 are displayed as 0.
When the value is divided by 10 or by 100 it is displayed in turn with "M 10" or
"M100".
4.3.14.2 - Description of Runtimes 2 menu
ITEM #
FORMAT
0
-
1
nn
2
nn
3
nn
4
nn
COMMENTS
When selected this item
authorises return to the
previous menu
Unit operating hours*
Unit operating hour in cooling
mode
Unit operating hours in heating
mode
Compressor A1 operating
hours*
Compressor A2 operating
hours*
Compressor B1 operating
hours*
Compressor B2 operating
hours*
Machine starts*
Compressor A1 starts*
Compressor A2 starts*
Compressor B1 starts*
Compressor B2 starts*
Evaporator pump #1 operating
hours*
Evaporator pump #2 operating
hours*
Condenser pump #1 operating
hours*
Condenser pump #2 operating
hours*
Open-loop condenser pump
operating hours*
UNITS
DESCRIPTION
-
When selected this item
authorises return to the
previous menu
-
Compressor starts for
compressor with most starts
during the last hour
-
24 hours average number of
starts/hour, compressor
minutes
Minimum compressor
operating time during last
hour
minutes
24 hours average minimum
operating time above