Checking Ionisation Current - Viessmann MatriX radiant burner Service Instructions Manual

Pressure jet gas burner (type vm iii) for vitocrossal 300 (type ct3) rated output 170
Table of Contents

Advertisement

Further details regarding the individual steps

Checking ionisation current

1. Switch OFF the mains electrical
isolator.
2. Pull ionisation cable plug C off.
3. Switch ON the mains electrical
isolator.
There must be a fault shutdown
after a burner start has been
attempted. Display B flashes fault
code F 25.
4. Switch OFF the mains electrical
isolator.
Please note:
Test cable no. 1 is required when
checking with Testomatik−Gas
equipment.
You can also carry out this check with
a multimeter.
5. Push plug C of the ionisation
current lead into adaptor D.
Initial start−up, inspection and maintenance
A
D
C
(cont.)
6. Plug socket A of the test lead
onto the ionisation electrode.
7. Switch the mains electrical
isolator ON and check the
ionisation current.
Please note:
Ionisation current
H min. 10 mA approx. 2 to 3 s after
opening the gas valve,
H min. 30 mA at full load,
H min. 5 mA at partial load.
8. Record the actual values in the
service report (from page 42).
9. Switch the mains electrical
isolator OFF , remove the test
equipment and reconnect the
plug connector of the ionisation
cable.
10. Switch ON the mains electrical
isolator.