7) Insert the positive and negative connectors into the inverter DC input terminals respectively,
and a "click" sound represents the assembly in place, as shown in Figure 4-12:
4.3.2 Connection of AC output
The RECOM RCM 4~25-TP-D series three phase inverter applies to the three-phase power grid
with a voltage of 230/400V and a frequency of 50/60Hz.
The recommended cable and AC breaker for the RECOM RCM 4-25TP-D series three phase
inverter are shown in the following table:
RCM-4-
RCM-5-
Model
TP-D
TP-D
Copper
2.5
Cable
-10mm
-10mm
2
Breaker
20A
Warning
4.3.2.1 AC connector connection steps
1) Take the AC connector out of the accessory bag and disassemble it, as shown in Figure 4-13:
C a b l e Gl a n d
RCM-6-
RCM-8-
TP-D
TP-D
2.5
2.5
3.2
-10mm
-10mm
2
2
20A
20A
20A
An AC breaker must be connected on the AC side of the inverter.
Any loads cannot be directly connected to the inverter.
T hrea d e d S l ee ve
Figure 4-12
RCM-10-
RCM-12-
TP-D
TP-D
4-10mm
6-10mm
2
2
2
32A
32A
Figure 4-13
RCM-15-
RCM-17-
RCM-20-
TP-D
TP-D
6-10mm
8-10mm
8-10mm
2
2
32A
40A
AC Ter mi n al H ead
RCM-25-
TP-D
TP-D
8-10mm
2
2
40A
50A