Installation Verification; Checking The Indoor Unit - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual

5.1 Checking the Indoor Unit

After the installation, check the items listed in
5-3, and record the check results.
Table 5-1 Cabinet checklist
Check Item
Cabinet
Fan
(Optional)
Wet film
humidifier
Compressor
Issue 08 (2021-09-17)
5

Installation Verification

Expected Result
The cabinet is installed properly, without
any tilts.
The cabinet is secured to the bottom base
using bolts as required.
The foreign matter inside the cabinet such
as cable ties and stubs is cleaned up.
The fan is secured.
The fan has no foreign matter inside.
The fan blades rotate properly.
The water inlet solenoid valve is secured
reliably and steadily.
The wet film is secured reliably and
steadily.
Water inlet pipes are connected securely
without leaks.
The sheet metal for transporting the
compressor is removed.
The bolts on the compressor are
tightened.
Copyright © Huawei Technologies Co., Ltd.
5 Installation Verification
Table
5-1,
Table
5-2, and
Actual Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
Table
116