INSTALLATION INSTRUCTIONS
to. Refer to the appropriate Vent Termination section above for
locating the vent termination
If the unobstructed distance from the foundation to the property
line of the adjacent lot is no less than 4 ft. (1.2 M) and no
greater than 8 ft. (2.4 M), it will be necessary to re-direct the
flue gas plume. In this situation, a concentric vent kit cannot be
used. A 2-pipe termination (or single pipe termination when
permitted) that re-directs the flue gas away by use of an elbow
or tee, certified to ULC S636 from the adjacent property line
must be used. See Figure 56.
Size the Vent and Combustion Air Pipes
General
Vent and
1−1/2−in.
Combustion Air
Pipe Diameters
1−1/2−in. (38 mm)
2−in. (51 mm)
2−1/2−in. (64 mm)
3−in. (76−mm)
4−in. (102 mm)
Furnace combustion air and vent pipe connections are sized
for 2-in. (50 mm ND) PVC/ABS DWV pipe. The combustion air
and
vent
pipe
connections
polypropylene venting systems with outside diameters of
approximately 60 mm (2−3/8 inches). Any pipe diameter
change should be made outside furnace casing in vertical pipe.
Any change in diameter to the pipe must be made as close to
the furnace as reasonably possible (see Figure 41).
The Maximum Vent Length for the vent and combustion air pipe
(when used) is determined from the Maximum Equivalent Vent
Length in Table 14, minus the number of fittings multiplied by
the deduction for each type of fitting used from Table 15.
FURNACE
NOT IN
HORIZONTAL
SECTION
Figure 41 − Combustion−Air and Vent Pipe Diame-
ter Transition Location and Elbow Configuration
NOTICE
OPTIONAL CONFIGURATION FOR COMBUSTION
AIR INLET PIPE
In applications where there is a risk of excessive mois-
ture entering the combustion air inlet pipe, a moisture
trap may be added to the inlet pipe to help prevent
moisture from entering the furnace from the combus-
tion air inlet pipe. See Figure 58.
When sizing venting systems, the equivalent length of
the optional moisture trap (15 feet/5 M) must be taken
into account.
440 01 6001 05
Approved Two−Pipe Termination Fittings
2−in.
(38 mm)
(51 mm)
No
Yes
No
Yes
No
No
No
No
No
No
also
accommodate
60mm
PIPE DIAMENTER
TRANSITION IN
SECTION
A93034
Specifications subject to change without notice.
The concentric vent kit currently cannot be modified to attach
an elbow to the vent portion of the rain cap. A tee attached to
the rain cap could potentially direct the flue gas plume toward
the intake air stream and contaminate the incoming combustion
air for the furnace.
Refer to Figure 56 for terminations approved for use in Alberta
and Saskatchewan.
2−1/2−in.
3−in.
(64 mm)
(76−mm)
No
No
No
No
No
Yes
No
Yes
No
Yes
Combustion Air Inlet Moisture Trap
To prevent moisture from trickling into the furnace vestibule, a
trap can be installed in the intake air pipe near the furnace.
Connecting a drain line to the trap is recommended as trace
amounts of moisture will evaporate into the intake air stream. If
the combustion air inlet is located near a moisture exhaust
duct, or there are other concerns of excessive moisture being
drawn into the combustion air inlet, it is encouraged to connect
a drain line to the trap.
The trap can be constructed from a running tee of the same
diameter of the intake air pipe with EITHER a removable cap
attached to a 6-inch long pipe connected to the tee or the
External vent Trap Kit to help prevent contaminants from
entering the furnace. See
The External Vent Trap Kit accessory may be used as a trap for
the combustion air inlet pipe if a large amount of moisture must
be removed. The drain line may be connected to the same
drain as the furnace condensate and the evaporator coil
condensate line ONLY if the inlet air trap drain and the
evaporator coil drain empty into an open segment of pipe
Figure 12
above the drain, See
Trap Kit, refer to those instructions for proper drain
connections.
The tee may also be connected to the intake air pipe on the
Figure 58
side of the casing. See
In any configuration, it will be necessary to add the equivalent
length of the tee (15 feet/5 M) to the Total Equivalent Vent
Length of the venting system.
Gas Furnace: R9MSB
Allowable
4−in.
Concentric Vent
(102 mm)
Kit
No
2−in. (51 mm)
No
2−in. (51 mm)
2−in. (51 mm)
No
3−in. (76 mm)
No
3−in. (76 mm)
Yes
3−in. (76 mm)
Figure 58
.
. When using the External Vent
.
43