Plumbing Applications; Recirculation System - Noritz GQ-C5032WZ US Installation Manual

Condensing tankless gas water heater
Hide thumbs Also See for GQ-C5032WZ US:
Table of Contents

Advertisement

12.

Plumbing Applications

Condensing
Tankless Gas
Water Heater
Isolation
Kit(*4)
Relay for Pump
(if larger than 85 Watts)
Hot Water
Combination Potable Water and Space Heating System
If the Air Handler does not control the water flow automatically, the Scale detection feature will not work.
Condensing
Tankless Gas
Water Heater
Isolation
Kit(*1)
32

Recirculation System

Cold Water Supply
Fixtures
Expansion Tank
(Install according
to local code)
Gas Supply
Globe
Aquastat(*3)
Valve
Pump Control Signal(*2)
Optional 8-10 Gallon
Storage Tank
(To alleviate cold water sandwich)
Pump(*2)
Check
Valve(*3)
Gas Supply
Hot Water
Notes:
1. Size the pump to provide a maximum of 2 GPM
Hot Water Return
2. Pump Control Signal is the preferred method
3. Set the Aquastat to 10˚F below the set output temperature.
4. Noritz recommends the use of an Isolation Kit
Pump(*1)
Notes:
1. Noritz recommends the use of an Isolation Kit with
the installation.
These kits include an integrated shut-off and service
valve with unions and a pressure relief valve.
Air Handler
2. Size the pump to provide a maximum of 3 GPM
(11.3 L/min.) with a head pressure equal to the loss
through the water heater and Air Handler.
3. Check valve required if it is not included with the pump.
4. Set the flow switch to deactivate the Air Handler when
the domestic hot water flow reaches 3 GPM (11.3 L/min.).
Adjust as necessary to prevent cycling.
5. If the system requires water for space heating at a higher
temperature than for other uses, means such as a
mixing valve shall be provided to temper the water for
the other uses to help prevent scalding.
6. Expansion tank required if a backflow preventer is installed.
7. The water heater cannot be used for space heating
applications only.
Flow Switch(*4)
Optional
Expansion Tank(*6)
Mixing Valve(*5)
(7.5 L/min.) through the system at 10 ft (3m) of
head plus piping losses.
Adjust the flow using a globe valve and verify the
flow rate with the maintenance monitors.
to control the recirculation pump.
For pumps larger than 85W, a relay connection
must be used. If the Pump Control Signal is not
used, an Aquastat may be used to control the pump.
An aquastat is the minimum pump control requirement
in order to maintain the full recirculation waranty.
with the installation.
These kits include an integrated shut-off and serv-
ice valve with unions and a pressure relief valve.
Pump
120VAC
Neutral
Ground
Live
Aquastat Wiring
Use Honeywell Aquastat
(Model L6006A or L6006C)
Backflow Preventer
(optional)
Cold Water
Supply
Fixtures
105
R
B
S
W

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecotough nrc98dv

Table of Contents