Available control settings – Advance Mode
Figure 23 SlimFit
control settings available in ADVANCED MODE (see Boiler Manual for BASIC MODE settings)
Menus and Items
BOILER SETTINGS Menu
• BOILER MODEL
• CONTROL TYPE
• HIGH ALTITUDE
• HIGH LIMIT TEMP
• WWSD TEMP
• ADJUST OUTDOOR
• CIRCULATOR EXERCISING
• FREEZE PROTECT CIRCS
• RESET FACTORY DEFAULT
PRIORITY menus
(page 52)
• INPUTS ASSIGNED
• SYSTEM TYPE
• TARGET MOD SENSOR
• TARGET ADJUST
• SUPPLY MAX
• SUPPLY MIN
• OD RESET MAX
• OD RESET MIN
• VOLTS FOR MAX
• VOLTS FOR MIN
• BOOST TIME
• SYSTEM OFF DIFF
• SYSTEM ON DIFF
• MAX BLR TEMP
• ADD BLR DIFF
• DROP BLR DIFF
• MOD DELAY TIME
• STABILIZE TIME
• ADD DELAY TIMER
• DROP DELAY TIMER
• BOILER ON DIFF
• BOILER OFF DIFF
• MAX ON TIME
• MIN ON TIME
• RUN BOILER PUMP
• RUN AUX PUMP/OUTPUT
• PRE PUMP
• POST PUMP
• MAX RATE (Local priorities only)
• MIN RATE
• MAX SYS MBH (Network priorities only)
• MIN BOILERS (Network priorities only)
See detailed information about controls settings (parameters) on the following pages.
Part number 550-100-569/0321
&
&
Default setting
(page 47)
ONLY BOILER CIRCULATOR ON
Default setting
Varies by priority
Varies by priority
Varies by system type
Varies by system type
Varies (5 or 10°F)
Equals
Varies by system
Varies by system
:
%
Factory set
Single
No
200°F
70°F
0°F
ALL ON
Varies
Varies
70°F
0°F
10V
0V
OFF
10°F
SUPPLY MAX
5°F
5°F
2 minutes
5 minutes
60 seconds
60 seconds
5°F
5°F
30 minutes
15 minutes
OFF
30 seconds
96%
20%
AUTO
1
Advanced Manual
Range/options
All SlimFit models available
Single, Master or Shadow
Yes or No
50 to 200°F
OFF, 50–100°F
-10 to +10°F
ON or OFF for each circulator
ON or OFF for each circulator
Range/options
1, 2, 3
See Figure 24, page 45 for choices
System Supply or Boiler Out
None, 0–10V, or ODT
60 to 190°F
60 to 190°F
50 to 100°F
-20 to 50°F
5V-10V
0V-4.9V
OFF, 1 to 240 minutes
2 to 15°F
2 to 15°F
60 to 190°F
2 to 10°F
2 to 10°F
1 to 15 minutes
3 to 30 minutes
30 to 240 seconds
30 to 240 seconds
2 to 20°F
2 to 10°F
OFF, 1 to 240 minutes
OFF, 1 to 240 minutes
YES or NO
YES or NO
OFF, 1 to 240 seconds
OFF, 1 to 240 seconds
100% to 21%
20% to 99%
AUTO or 100 to 32,000 MBTU's
1 to 8
– 43 –