UTICA BOILERS Trifire 3 Series Installation, Operation & Maintenance Manual page 54

Table of Contents

Advertisement

Table 17 - Carlin (CHIMNEY VENT) Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test
instruments.
Table 17- CARLIN CHIMNEY VENT PRELIMINARY BURNER SETTINGS
Boiler
Insertion
Firing
Depth
Model
4075
4.56"
4090
4.56"
5100
3.00"
5120
3.00"
6130
3.00"
6145
3.00"
Timings
Pre-purge
15 seconds
Post-purge
15 seconds
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Combustion
Rate
Liner
0.75
Oval
0.90
Oval
1.00
None
1.20
None
1.30
V6
1.45
V6
Nozzle
Nozzle
Mfr.
Type
Delavan
0.60 x 60B
Delavan
0.75 x 70A
Delavan
0.75 x 45B
Delavan
1.00 x 60A
Delavan
1.00 x 70A
Delavan
1.10 x 70B
54
Pump
Head Bar
Pressure
Setting
[PSI]
160
1
145
2
175
0.75
165
0.85/1.00
170
0.85/1.00
190
1.10/1.25
ECR Oil
Carlin Oil
Boiler
Burner
Burner
Model
Model
Number
4075
EZ-Select
240013299
4090
EZ-Select
240013299
5100
EZ-LF
240013406
5120
EZ-LF
240013406
6130
EZ-LF
240013408
6145
EZ-LF
240013408
PN 240013415 REV A [08/15/2021]
Rated
Air Band
AFUE
Setting
Efficiency
[%]
22%
87.0
28%
86.0
36%
87.0
40%
86.0
50%
87.0
50%
86.0
Part

Advertisement

Table of Contents
loading

Table of Contents