Water Circuit Design - LG MULTI V WATER MINI Engineering Manual

Table of Contents

Advertisement

Figure 17: Open-Type and Closed-Type Tower Design Schematic.
Open-Type
Cooling Tower
First Side
Heat Exchanger
Open-Type Cooling Tower + Heat Exchanger
Heat exchanger is installed between the cooling tower and water
source unit system piping, and the temperature difference between
the first and second sides is maintained constantly.
When using an open cooling tower or open geothermal wells, an intermediate heat exchanger is recommended to be installed to protect the water
source unit from contamination.
Expansion Tank
All closed loop systems must have a bladder type expansion tank installed. The expansion tank will protect the equipment from excess pres-
sures due to expansion and contraction of water in the loop as the temperature changes.
Heat Source and Storage Tank
There are several sources for heat that can be used for this system. They include the following:
• Electric boiler
• Gas boiler
• Solar heat with storage tanks
• Ground source heat
• Steam heat from remote central plant
To deal with thermal flux of the system, if floor space is allowed, a heat storage tank can be installed. The heat storage tank can store
surplus heat or store heat at nighttime when electric rates are lower. Closed type storage tanks are recommended to prevent contamination
of the water system.
Geothermal Water Circuit Design
In lieu of a cooling tower / boiler, Multi V Water Mini units may use a geothermal system that is properly sized to match the water cooled unit
capacity. This year round heating and cooling system will utilize a two (2) pipe closed loop water circuit that circulates water continuously,
maintaining water temperatures between 23°F and 113°F for heating, 23°F and 113°F for cooling (Variable water flow control kit [PRVC1]
required for all entering water temperatures; one kit per frame). When the Multi V Water Mini unit is in cooling mode, heat is rejected to the
geothermal system. When the Multi V Water Mini unit is in heating mode, heat is absorbed from the geothermal system.
Multi V Water Mini units have factory-installed stainless steel plate heat exchangers. To protect these heat exchangers, it is recommended to
use closed geothermal water loops. If open geothermal systems be used, an intermediate heat exchanger must be installed to isolate Multi
V Water Mini units from contaminants in the water system. Open geothermal loops may contain minerals, biological contaminants, corrosive
agents, or other substances which can cause scale, fouling or corrosion, that could degrade performance or shorten the life of the heat
exchanger and unit.
If entering water temperature falls below 42°F, glycol must be added to the system. Refer to antifreeze information on page 45 for recom-
mended levels of antifreeze and correction factors.
WATER CIRCUIT INSTALLATION
Second
Side
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Closed-Type
Cooling Tower
Closed-Type Cooling Tower
Heat-source water of the cooling tower is supplied directly to the
water source unit system.

Water Circuit Design

WATER CIRCUIT | 43