General Data; Electrical Data - LG MULTI V WATER MINI Engineering Manual

Table of Contents

Advertisement

Table 2: ARWN053GA2 Water Mini Unit Specifications.
Unit Model Number
Nominal Capacity / Input Power
Cooling Capacity (Btu/h)
1
Cooling Input Power (kW)
Heating Capacity (Btu/h)
1
Heating Input Power (kW)
Compressor
Type
Power Supply (volt/hz/phase)
MCA (A)
MOP (A)
System Data
Sound Pressure (dBA)
3
Heat Rejected to Equipment Room (Btu/h)
Net Weight (lbs.)
Shipping Weight (lbs.)
Dimensions (W x H x D)
Max. Qty Indoor Units
Refrigerant Piping Connections
Vapor Line OD (in.)
Liquid Line OD (in.)
Expansion Device
Factory Refrigerant Charge (R410A [lbs.])
Water Side
Heat Exchanger
Water Volume in Heat Exchanger (gal.)
Water Inlet/Outlet Connection Size (in)
Nominal Flow Rate Total (GPM)
Range of Flow (GPM)
Entering water temp. range (°F)– Cooling
Entering water temp. range (°F)– Heating
Total Heat of Rejection (Btu/h)
Total Heat of Absorption (Btu/h)
Pressure Drop (ft)
Maximum Water Pressure (psi)
ΔT (°F)
6
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
1
Current certified ratings are available at www.ahridirectory.org.
Power wiring is field provided, solid or stranded, and must comply with the applicable local and national
2
codes.
Sound pressure levels are tested in an anechoic chamber under ISO 3745 standard.
3
LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must
4
verify the shop drawing design against the as built design using LATS. Contractor must also use LG
manufactured Y-Branch and Header Kits only.
Table 3: ARWN053GA2 Water Mini Unit Electrical Data.
Nominal Tons
Unit Model No.
4.4
ARWN053GA2
MCA = Minimum Circuit Ampacity.
MOP = Maximum Overcurrent Protection is calculated as follows: (Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down to the nearest standard fuse size.
Allowable voltage range is between 208–230 volts only (tolerance is 10%).
Maximum allowable voltage imbalance is 2%.
2
4
5
5
Compressor Qty.
1
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

GENERAL DATA

Specifications / Electrical Data
ARWN053GA2
Inverter Rotary
208-230 / 60 / 1
20-5/8 x 42-1/2 x 13-1/8
Electronically Controlled (EEV)
Stainless Steel Plate
Variable water flow control kit (PRVC1) is required for all entering water temperatures (one kit per
5
frame). If entering water temperatures fall below 42°F, glycol must be added to the system.
Value is calculated as follows: Δt = Total Heat of Rejection/(Nominal Flow Rate x 500).
6
Communication cable between WSU to IDUs to be 18 AWG, 2-conductor, twisted, stranded, shielded.
7
Ensure the communication cable shield is properly grounded to the WSU chassis only.
ground the WSU to IDUs communication cable at any other point. Wiring must comply with all ap-
plicable local and national codes.
Compressor Motor RLA
21.6
4.4 Ton
52,900
3.2
61,400
3.5
27
45
54
512
168
181
9
3/4 Braze
3/8 Braze
2.2
0.2
1-1/4 FPT
15.9
8.3-19.9
23-113
23-113
56,640
49,448
9.5
640
7
MSC
MCA
-
27
PRODUCT DATA | 11