Menu: Pumps; Menu: External Connections - Bosch HPC 410 Installation Instructions For Contractors

User interface
Table of Contents

Advertisement

Menu item
Control range: Function description
Pumps
Make the circulation pump settings in this menu (
Chapter 4.1.2).
External
If used, do the settings for external connections in this
connections
menu ( Chapter 4.1.3).
Fuse size
If change needed after commissioning, set the main fuse
size for the house.
Manual defrosting [Yes]: The heat pump is forced to defrost the evaporator.
Smart grid
If used, do the settings for the smart grid in this menu (
Chapter 4.1.4).
PV system
If used, do the settings for the PV system in this menu (
Chapter 4.1.5).
Fixed temperature Use this setting if a buffer cylinder with integrated DHW
heating is installed. The heat pump will heat the cylinder to
a set temperature independent of outdoor temperature. All
heating circuits must be controlled by mixing valves.
Central fault
[All faults and messages]: All faults and messages
indicated will be displayed.
[Only faults]: Only faults indicated will be displayed.
Low-noise
[Silent mode on]
operation
• [No]: The heat pump will always run in normal
operation.
• [Auto]: The heat pump will run in low noise mode
during the set time period.
• [On]: The heat pump will always run in low noise mode.
If [Auto] is activated the heat pump will run in reduced
sound operation during the set time period.
• [Low-noise operation of]: set the start time for the low
noise operation.
• [Low-noise operation until]: set the stop time for the
low noise operation.
• [Min. outside temp.]: Below this outdoor temperature
the heat pump switches over to normal operation.
Table 2 Settings for the heat pump
4.1.2

Menu: Pumps

Make the circulation pump specific settings in this menu. These settings
are only available if the system is designed and configured accordingly
and the type of appliance used supports this setting.
Menu item
Control range: Function description
Prim. heating
[Automatic]: The primary circulation pump is in operation
pump mode
when any heat source is active. When all heat sources are
off, the circulation pump is also off.
[On]: The primary circulation pump is in operation
continuously.
Minimum flow rate The heat pump only starts once the minimum flow rate has
been reached.
Flow rate detect.
[On]: activates the flow control.
[Off]: deactivates the flow control.
Temp.diff. TC3/
3...7...10 K: Set the permissible temperature differential
TC0 Heat.
between the heat pump flow and return in heating mode.
Temp.diff. TC3/
2...3...10 K: Set the permissible temperature differential
TC0 Cool.
between the heat pump flow and return in cooling mode.
Table 3 Settings in the heat pump data menu
HPC 410 – 6721832682 (2021/02)
4.1.3

Menu: External connections

Make the specific settings for each external connection in this menu.
Multiple settings is possible in each menu.
The ESC blocking time1 on menu items are only available in the
External connection 1 menu. If any of these items are set to "On" the
smart grid function is automatically activated for External connection 4
and no other settings can then be done in that menu.
Menu item
Control range: Function description
Logic ext.
[Closed (NO)]: Open contact is interpreted as On.
connection 1...4
[Open (NC)]: Closed contact is interpreted as On.
[Block compr. operation]:
An active signal on the external input blocks the
compressor operation.
[Block HW operation]:
An active signal on the external input blocks the DHW
operation.
[Block heating mode]:
An active signal on the external input blocks the heating
operation.
[Block cooling mode]:
An active signal on the external input blocks the cooling
operation.
[Overheat. protection HC1]:
An active signal on the external input blocks the heating
operation and indicates a fault.
[ESC blocking time1 on]:
An active signal on the external input blocks compressor
and additional heater operation.
[ESC blocking time2 on]:
An active signal on the external input blocks compressor
operation.
[ESC blocking time3 on]:
An active signal on the external input blocks additional
heater operation.
[Block additional heater]:
An active signal on the external input blocks additional
heater operation.
[PV system]:
An active signal on the external input indicates that there
are photovoltaic energy available. Heating and DHW
temperatures will be adjusted according to the settings
made in the [PV system] menu.
Table 4 Settings in the heat pump data menu