Eaton Greengate NeoSwitch ONW-D-1001-MV-W Installation Instructions

Dual technology single relay occupancy sensing wall switch

Advertisement

Quick Links

P/N 9850-000323-01
General Information
• Read all instructions on both sides of this
• Install in accordance with ALL local codes
sheet first
• For indoor use only
Specifications
Technology: Passive Infrared (PIR) and Ultrasonic (US)
Coverage: Major motion – 1000 sq. ft.
Electrical Ratings:
120 VAC:
Light Level Sensing: 0 to 200 foot-candles
• Incandescent/Tungsten –
Operating Environment:
Max. load: 6.7 amps, 800W, 50/60 Hz
• Temperature: 32° F – 104° F (0° C – 40° C)
• Fluorescent/Ballast –
• Relative Humidity: 20% to 90% non-condensing
Max. load: 10 amps, 1200W, 50/60 Hz
Housing: Durable, injection molded housing. ABS resin
Motor Load: ¼ HP @ 125 VAC
complies with UL 94VO.
277 VAC:
Size:
• Fluorescent/Ballast –
• Mounting Plate/Strap Dimensions:
Max. load: 9.8 amps, 2700W, 50/60 Hz
4.195" H x 1.732" W (106.553 mm x 44 mm)
Ballast Compatibility: Compatible with magnetic and
• Product Housing Dimensions: 2.618" H x 1.752"
electronic ballasts
W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)
No Minimum Load Requirement
LED Indicators: Red LED indicates PIR detection;
Time Delays: Self-Adjusting, 15 seconds/test (10 min
Green LED indicates Ultrasonic detection.
Auto), Selectable 5, 15, 30 minutes
Description
The ONW-D-1001-MV Occupancy Sensing Wall Switch is a Passive Infrared (PIR) and Ultrasonic (US) motion
sensing lighting control and conventional wall switch all-in-one, used for energy savings and convenience.
The sensor combines PIR and US technologies to monitor a room for occupancy.
PIR Technology
The sensor's segmented lens divides the field of view into sensor zones, and detects the changes in temperature
that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.
US Technology
The sensor produces a low intensity, inaudible sound. It detects occupancy from changes in the acoustic waves
caused by motion, such as reaching for a telephone, turning a page in a book, walking into a room, turning in a
swivel chair, etc. The sensor does not respond to audible sound.
Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications thus saving additional
energy. PIR is used to turn the lights ON and then either or both technologies are used to keep the lights ON.
The ONW-D-1001-MV allows the control of one load with one occupancy sensor switch.
The sensor can be configured to enhance energy savings by setting the unit for Manual ON operation.
In Automatic ON Mode, the lights turn ON automatically when a person enters the room. In Manual ON Mode, the
lights are turned ON by pressing the universally recognized light icon pushbutton. In either mode, the lights stay ON
as long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF automatically after a
preset time delay interval.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and time
delay in real-time. By adjusting sensitivity and time delay automatically, the sensor is maximizing the potential energy
savings that are available in the particular application.
The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.
Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy. The
sensor will switch the lights ON when it detects a person entering the area. If the sensor does not continue to detect
motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute time delay.
ON/OFF Button Disable Option – When selected this option disables the ON/OFF button(s) and sensor becomes
automatic only control.
NeoSwitch Dual Technology Single Relay
Occupancy Sensing Wall Switch
(Ground Required)
Coverage
The ONW-D-1001-MV is designed for offices up to 300 square feet.
Minor motion – 300 sq. ft.
,
8
,
8
,
10
Location
When installing the ONW-D-1001-MV in a new junction box, choose the switch location carefully to provide optimum
coverage of the occupied area. When replacing an existing wall switch, bear in mind that there must be a clear line-
of-sight between the sensor and the area to be covered. Avoid pointing the ONW-D-1001-MV directly into the hallway
where it may detect passers-by.
,
36
,
20
Minor Motion, IR
Major Motion, IR
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
,
15
,
20
Installation Instructions
Model # ONW-D-1001-MV-W
Model # ONW-D-1001-MV-V
Model # ONW-D-1001-MV-LA
Model # ONW-D-1001-MV-G
Model # ONW-D-1001-MV-B
Installation
The ONW-D-1001-MV can be installed in any standard single gang box. It may be
installed in the same manner as an ordinary wall switch.
• Wire the ONW-D-1001-MV as described in the wiring section
• Mount the ONW-D-1001-MV in the junction box
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked "SWD." All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. (Use twist-on wire connectors for
all connections.)
3. Mount unit to wall box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install wall switch plate.
Wiring Diagram 1:
120/277 VAC
BLACK
120/277 VAC single level
single circuit wiring diagram
GREEN
GROUND
NEUTRAL
Wiring Diagram 2:
BLACK
120/277 VAC
120/277 VAC single level
switch dual level wiring using a
toggle switch wiring diagram
GREEN
GROUND
NEUTRAL
A/B SWITCHING USING TOGGLE
SWITCH TO TURN OFF SECOND LOAD
BLUE
LOAD
BLUE
LOAD 1
LOAD 2
Eaton's Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com

Advertisement

loading

Summary of Contents for Eaton Greengate NeoSwitch ONW-D-1001-MV-W

  • Page 1 GREEN savings that are available in the particular application. LOAD 1 LOAD 2 The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light. GROUND Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy. The sensor will switch the lights ON when it detects a person entering the area. If the sensor does not continue to detect motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute time delay. NEUTRAL ON/OFF Button Disable Option – When selected this option disables the ON/OFF button(s) and sensor becomes automatic only control. A/B SWITCHING USING TOGGLE SWITCH TO TURN OFF SECOND LOAD Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com...
  • Page 2 ON/OFF Button note LED and go to Installer Adjustments – Sensitivity Switch legend. Adjustments section) Reset sensor time delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, 4. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer Adjustments Section) and then back to its original position) 5. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section) 6. At this point you can exit the room and let the sensor time-out. When the sensor times-out and is OFF with power ON for five Override minutes, the unit will go to a 10 minute Time Delay user mode setting. The Override setting allows the sensor to operate as a service switch in the unlikely event of failure. 1. Move DIP Switch 12 up. Note: To place into Test Mode, toggle DIP Switch 12 out of its current position, wait 3 seconds, and then back into its original position. 2. The pushbutton can be used to manually turn lights ON or OFF. Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 Printed in Malaysia www.coopercontrol.com...

This manual is also suitable for:

Greengate neoswitch onw-d-1001-mv-vGreengate neoswitch onw-d-1001-mv-laGreengate neoswitch onw-d-1001-mv-gGreengate neoswitch onw-d-1001-mv-b