ENVIRONMENTAL RATINGS:
Ambient Temperature:
Operating: -40° F to 140° F.
Storage: -40° F to 150° F.
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
DIMENSIONS: Refer to Figs. 1 and 2.
Plug-in Flame Signal Amplifiers
Self-
Type
Color
Checking
Rectification
Green
No
No
No
Dynamic
AMPLI-
CHECK™
Dynamic
AMPLI-
CHECK™
Dynamic
AMPLI-
CHECK™
Dynamic
Self-
Check
Infrared
Red
No
Dynamic
AMPLI-
CHECK™
Ultraviolet
Purple
No
Dynamic
AMPLI-
CHECK™
Blue
Dynamic
Self-
Check
a
The C7012A,C, C7027, C7035 and C7044 flame detectors should be used only on burners that cycle on-off at least
once every twenty-four hours. Appliances with burners that remain on for twenty-four hours continuously or longer
should use the C7012E,F Flame Detector with the R7847C Amplifier or the C7076A Flame Detector with the
R7886A Amplifier as the ultraviolet flame detection system.
b
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute
during burner operation and shuts down the burner if the detection system fails.
c
Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the
burner if the amplifier fails.
d
Order flame rod separately; see holder Instructions.
e
Use only Honeywell Photocell, part no. 38316.
TABLE 2—FLAME DETECTION SYSTEMS (Figs. 3, 4, 5)
Flame
Failure
Response
Model
Time
R7847A
.8 or 3 sec
R7847A
.8 or 3 sec
R7847A
3 sec
c
R7847B
.8 or 3 sec
c
R7847B
.8 or 3 sec
c
R7847B
3 sec
b
R7847C
3 sec
R7848A
3 sec
c
R7848B
3 sec
R7849A
.8 or 3 sec
c
R7849B
.8 or 3 sec
b
R7886A
3 sec
WEIGHT: RM7840 with Dust Cover: 1 pound 13 ounces,
unpacked.
IMPORTANT: Flame Detection System available for
use with RM7840. To select your Plug-in Flame
Signal Amplifier and matching Flame Detector, see
Table 2.
Applicable Flame Detectors
Fuel
Type
Gas
Rectifying
Flame Rod
Holders
Oil
Rectifying
Photocell
Gas, oil,
Ultraviolet
coal
(PurplePeeper)
Gas
Rectifying
Flame Rod
Holders
Oil
Rectifying
Photocell
Gas, oil,
Ultraviolet
coal
(Purple
Peeper)
Gas, oil,
Ultraviolet
coal
(Purple
Peeper)
Gas, oil,
Infrared
coal
(Lead Sulfide)
Gas, oil
Infrared
coal
(Lead Sulfide)
Gas, oil
Ultraviolet
(Minipeeper)
Gas, oil
Ultrviolet
(Minipeeper)
Gas, oil,
Ultraviolet
coal
(Adjustable
Sensitivity)
3
RM7840E,G,L,M
SPECIFICATIONS
Models
C7004,
C7007,
d
C7011.
CompleteAssemblies:
C7008, C7009, Q179.
C7003, C7010,
e
C7013, C7014.
a
C7012A,C.
C7004, C7007,
C7011.
d
Complete Assemblies:
C7008, C7009, Q179.
C7003, C7010,
e
C7013, C7014.
a
C7012A,C.
C7012E,F.
C7015.
C7015.
C7027, C7035,
a
C7044.
C7027, C7035,
a
C7044.
C7076.
65-0087—2