RUN
1. A ten second stabilization period occurs at the
beginning of the RUN period.
2. The firing rate motor releases to modulation
(RM7840E,G,L).
3. The RM7840 is now in RUN and will remain in
RUN until the controller input, terminal 6, opens, indicat-
ing that the demand is satisfied or a limit has opened.
POSTPURGE
The RM7840 provides a fifteen second POSTPURGE
following the completion of the RUN period. The blower
Fig. 17—RM7840E,L sequence.
INITIATE
STANDBY
POWER
LED
DISPLAY
BURNER
OPERATING
CONTROLS
AND
INTERLOCK. CHECK
INTERLOCKS
1
FLAME
SIGNAL
FIRING
RATE
MOTOR
1
FOR THE RM7840E: THE HIGH FIRE SWITCH MUST BE WIRED CORRECTLY TO PERFORM ENERGY SAVING PURGE
FUNCTIONS. THE BURNER/BLOWER MOTOR DOES NOT START UNTIL THE HIGH FIRE SWITCH HAS BEEN MADE.
PREPURGE
00
00
00
DRIVE TO
TIMED
HIGH FIRE
PURGE
POWER
POWER
POWER
PILOT
FLAME
MAIN
ALARM
BURNER/BLOWER MOTOR
1
LIMITS AND BURNER CONTROLLER CLOSED
LOCKOUT INTERLOCKS CLOSED
PREIGNITION INTERLOCK CLOSED
5
TO
19
HIGH FIRE SW.
SAFE START CHECK
RM7800E,L SWITCHING
13
12
TO
MOTOR ACTION
motor output is powered to drive all combustion products
and any unburned fuel from the combustion chamber. It
also supplies combustion air to burn fuel being purged
from the fuel line downstream of the fuel shutoff valve.
1. The main fuel valve and intermittent pilot valve,
terminals 9 and 21, are de-energized and the firing rate
motor is commanded to the low fire position to begin the
POSTPURGE period.
2. The Preignition Interlock closes within the first five
seconds of POSTPURGE.
3. After the fifteen second POSTPURGE period is
completed, the RM7840 reenters STANDBY.
RM7840E,L
PREPURGE
00
10
20
DRIVE TO
PFEP
LOW FIRE
4 OR 10 SEC
MFEP
POWER
POWER
POWER
PILOT
PILOT
PILOT
FLAME
FLAME
FLAME
MAIN
MAIN
MAIN
ALARM
ALARM
ALARM
10
IGN.
5 SEC.
10 SEC. IGN./PILOT 8
15 SEC. PILOT
21
MAIN VALVE
L1
TO
6
TO
TO
4
20
5
18
LOW FIRE SW.
TO
FLAME PROVING
13
14
TO
19
RM7840E,G,L,M
25
00
15
RUN
POSTPURGE
STANDBY
POWER
POWER
POWER
PILOT
FLAME
MAIN
ALARM
5
9
6
7
IC
PII
SSC
13
15
TO
13
TO
14
M3357
65-0087—2
OPERATION