Download Print this page

PCB Piezotronics IMI SENSORS Y685A19 Installation And Operating Manual

Mechanical switch with remote reset solenoid and 24vdc powered.

Advertisement

Quick Links

Model Y685A19
Mechanical Switch with Remote Reset solenoid and 24VDC powered.
Installation and Operating Manual
For assistance with the operation of this product,
contact the PCB Piezotronics, Inc.
Toll-free: 800-959-4464
24-hour SensorLine: 716-684-0001
Fax: 716-684-3823
E-mail: imi@pcb.com
Web: www.imi-sensors.com

Advertisement

loading

Summary of Contents for PCB Piezotronics IMI SENSORS Y685A19

  • Page 1 Model Y685A19 Mechanical Switch with Remote Reset solenoid and 24VDC powered. Installation and Operating Manual For assistance with the operation of this product, contact the PCB Piezotronics, Inc. Toll-free: 800-959-4464 24-hour SensorLine: 716-684-0001 Fax: 716-684-3823 E-mail: imi@pcb.com Web: www.imi-sensors.com...
  • Page 2  Assistance is needed to safely operate equipment  PCB Piezotronics is an ISO-9001 certified company whose Damage is visible or suspected  calibration services are accredited by A2LA to ISO/IEC Equipment fails or malfunctions 17025, with full traceability to SI through N.I.S.T.
  • Page 3 CAUTION Refers to hazards that could damage the instrument. NOTE Indicates tips, recommendations and important information. The notes simplify processes and contain additional information on particular operating steps. The following symbols may be found on the equipment described in this manual: This symbol on the unit indicates that high voltage may be present.
  • Page 4 PCB工业监视和测量设备 - 中国RoHS2公布表 PCB Industrial Monitoring and Measuring Equipment - China RoHS 2 Disclosure Table 有害物质 镉 汞 铅 (Pb) 六价铬 (Cr(VI)) 多溴联苯 (PBB) 多溴二苯醚 (PBDE) 部件名称 (Hg) (Cd) 住房 PCB板 电气连接器 压电晶体 环氧 铁氟龙 电子 厚膜基板 电线 电缆 塑料 焊接...
  • Page 5 Component Name Hazardous Substances Lead (Pb) Mercury (Hg) Cadmium (Cd) Chromium VI Polybrominated Polybrominated Compounds Biphenyls (PBB) Diphenyl Ethers (Cr(VI)) (PBDE) Housing PCB Board Electrical Connectors Piezoelectric Crystals Epoxy Teflon Electronics Thick Film Substrate Wires Cables Plastic Solder Copper Alloy/Brass This table is prepared in accordance with the provisions of SJ/T 11364.
  • Page 6 Model 685A09/685A19/29/39 Mechanical Vibration Switch Operating Guide 3425 Walden Avenue, Depew, New York 14043-2495 Phone (716) 684-0003 Fax (716) 684-3823 Toll Free Line 1-800-959-4IMI MANUAL NUMBER: 56534 MANUAL REVISION: A ECN NUMBER: 43636...
  • Page 7: Table Of Contents

    Table of Contents Introduction ........................Page 3 General Features Warning Installation ........................Page 4 Internal Switches ......................Page 4 Remote Reset and Power On Delay ................Page 5-6 Setting Up The Switch ....................Page 6-7 Typical Installation Locations ..................Page 8-9 PAGE 2...
  • Page 8: Introduction

    Introduction The Mechanical Vibration Switch is a shock sensitive mechanism for shutdown of engine or electric motor powered equipment. This switch uses a patent pending linear adjustment magnetic latch technology to ensure reliable operation. Pushing the reset button moves the tripping latch into a magnetically held position. A shock/vibration will move the magnet beyond this holding position, thus freeing the spring loaded tripping latch to transfer the contacts and shut down the machinery.
  • Page 9: Installation

    Installation: The vibration switch is sensitive to shock and vibration in all three planes of motion – up/down, front/back and side/side. Side/side (in the same plane as the reset pushbutton) is the most sensitive. For maximum sensitivity, mount the unit so that the side with the reset button is in-line with the direction of rotation of the machine. The vibration switch must be firmly attached/mounted to the machine so that all mounting surfaces are in rigid contact with the mounting surface of the machine.
  • Page 10: Remote Reset And Power On Delay

    Chassis Screw Terminal Remote Reset and Power On Delay Models 685A19, 685A29 and 685A39 have provisions to reset the switch remotely. The vibration switch can be remotely reset after being tripped by applying the correct voltage across the reset terminal as shown below. NOTE: There is no positive/negative polarity needed for the wiring.
  • Page 11: Setting Up The Switch

    685A29 Only – A 120VAC power supply is needed to remotely reset the switch by energizing a solenoid. Upon applying 120VAC to the solenoid, the unit will need 184mA to energize the remote reset coil. At standard ambient temperature, the solenoid has a 25% “on” 75% “off” cycle. Maximum allowed On Time ( remote reset energized ) versus minimum Off Time ( remote reset de-energized ) On Time ( 25% ) Off Time ( 75% )
  • Page 12 Figure 1: Reset Button Figure 2: Sensitivity Adjustment Screw Figure 2A: Resetting the Switch Figure 2A: Adjusting the Sensitivity 3) Start the machine. 4) If the instrument trips on start-up, allow the machine to stop. Turn the sensitivity adjustment ¼ to ½ turn clockwise.
  • Page 13: Typical Installation Locations

    Typical Installation Locations Cooling Tower Fan and Motor Reciprocating Compressor PAGE 8...
  • Page 14 Vibratory Screens PAGE 9...
  • Page 15 Model Number Revision: A LINEAR ADJUST MECHANICAL VIBRATION SWITCH 685A19 ECN #: 51040 OPTION AL VERSION S Performance EN GLISH Optional versions have identical specifications and accessories as listed for the standard model except Measurement Range 7 g pk 68.7 m/s² pk where noted below.
  • Page 16 PCB Piezotronics Inc. claims proprietary rights in REVISIONS the information disclosed hereon. Neither it nor any reproduction thereof will be disclosed to others DESCRIPTION without the written consent of PCB Piezotronics Inc. ADDED NOTE 1 46319 SENSITIVITY ADJUSTMENT RESET SWITCH SCREW 3.70 [94.0]...