Mitsubishi Electric CITY MULTI PUMY-P112VKM5 Technical & Service Manual page 56

Split-type, heat pump air conditioners
Hide thumbs Also See for CITY MULTI PUMY-P112VKM5:
Table of Contents

Advertisement

Check code
Superheat due to low discharge temperature trouble
1500
(U7)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Continued from the previous page.
Is the resistance detected?
Check the voltage and appearance of the
indoor controller board.
Is the voltage normal?
Is it free from any trace of over-
heating or burning?
Check the 63HS voltage.
Is the voltage(*) detected?
OCH740
Diagnosis
Yes
Yes
*For the voltage, refer to ˝8-8. HOW
TO CHECK THE COMPONENTS˝.
Yes
No
Replace the indoor controller board.
No
No
Replace the outdoor multi controller circuit
board.
56
Chart 2 of 2
Remedy
Replace the indoor LEV.
Replace the 63HS.