9-2-2. Cross section area of Wire for Main Power and ON/OFF capacities
<Outdoor unit> <When power is supplied to outdoor unit and branch box separately>
Model
Outdoor Unit
P112–140VKM5
<Outdoor unit> <When power is supplied to branch box from the outdoor unit>
Model
Outdoor Unit
P112–140VKM5
1
*
A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
<Indoor units> When power is supplied to indoor unit and outdoor unit separately
Total operating current of the indoor unit
3
F0 = 16 A or less *
3
F0 = 25 A or less *
3
F0 = 32 A or less *
Apply to IEC61000-3-3 about max. permissive system impedance.
2
*
The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
3
*
Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 16)/C}
Connect to Branch box (PAC-MK·BC(B))
Indoor unit
Type 1
PEAD-RP·JA(L)Q, PEAD-M·JA(L), PEY-(S)P·JA
SEZ-KD·VAQ(L), SEZ-M·DA(L), PCA-RP·KAQ, PCA-M·KA, PLA-RP·BA,
Type 2
PLA-RP·EA, SLZ-KF·VA2, SLZ-M·FA, PLY-(S)P·BA, SEZ-KH·VALT,
PCY-(S)P·KA, PLA-M·EA
Type 3
MLZ-KA·VA, MLZ-KP·VF
MFZ-KJ·VE2, MSXY-FJ·VE, MSZ-LN·VG, MSZ-AP·VG(D), MSZ-AP·VF,
Type 4
MSZ-EF·VG-E2, MSZ-EF·VGK-E1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
MSZ-FH·VE, MSZ-SF·VE, MSZ-EF·VE, MSZ-SF·VA, MSZ-GF·VE,
Type 5
MSZ-GE·VA, MSZ-EF·VA, MSY-GE·VA, MSY-EF·VA, MSZ-FH·VA,
MSY-GH·VA, MSZ-FK·VA, MSZ-GC·NA, MSZ-EF·VG-E1
Type 6
Branch box (PAC-MK·BC)
Type 7
ecodan (Cylinder unit, Hydrobox)
4
*
This value may increase due to a locally connected actuator.
Connect to Connection kit (PAC-LV11M-J)
Indoor unit
MFZ-KJ·VE2, MSZ-LN·VG, MSZ-AP·VG(D), MSZ-AP·VF, MSZ-EF·VG-E2,
Type 8
MSZ-EF·VGK-E1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
MSZ-GE·VA(D), MSZ-SF·VA, MSZ-SF·VE, MSZ-EF·VE, MSZ-FH·VE,
Type 9
MSY-GE·VA, MSY-GH·VA, MSZ-EF·VG-E1
Type 10 Connection kit (PAC-LV11M-J)
Indoor unit
Type 11 PEFY-P·VMA(L)-E(2), PEFY-P·VMA3-E
Type 12 PEFY-VMHS-E-F, PEFY-P10-140VMHS-E
PMFY-VBM-E, PLFY-VBM-E, PLFY-VEM-E, PLFY-VFM-E1, PEFY-VMS1(L)-E,
Type 13
PCFY-VKM-E, PKFY-VHM-E, PKFY-VKM-E, PFFY-VKM-E2, PFFY-VLRMM-E,
PLFY-EP·VEM-E, PMFY-P·VFM-D, PKFY-VLM-E, PFFY-VCM-E
Type 14 PEFY-P·VMA(L)-E3, PEFY-M·VMA(L)-A
Type 15
PKFY·VBM-E
PLFY-VLMD-E, PEFY-VMR-E-L/R, PFFY-VLEM-E, PFFY-VLRM-E,
Type 16
PWFY-VM-E1(2)-AU, PEFY-P·VMH-E-F, GUF-RD(H)4
C: Multiple of tripping current at tripping time 0.01s
Please pick up ˝C˝ from the tripping characteristic of the breaker.
<Example of ˝F2˝ calculation>
Condition PEFY-VMS × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
5
Current sensitivity is calculated using the following formula.
*
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + ··· + V2 × (Quantity of Type16)
+ V3 × (Wire length[km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
2
1.5 mm
2
2.5 mm
2
4.0 mm
Notes:
1. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57).
For example, use wiring such as YZW.
5. install an earth line longer than power cables
OCH740
Power Supply
Main Cable
~/N 220-230-240 V, 50 Hz
~/N 220 V, 60 Hz
Power Supply
Main Cable
~/N 220-230-240 V, 50 Hz
~/N 220 V, 60 Hz
Minimum wire thickness (mm²)
Main Cable
Branch
1.5
1.5
2.5
2.5
4.0
4.0
V3
48
56
66
Minimum Wire Cross-sectional
area (mm²)
Branch
Ground
6
6
Minimum Wire Cross-sectional area (mm²)
Branch
Ground
6
6
Ground-fault interrupter *
Ground
1.5
20 A current sensitivity *
2.5
30 A current sensitivity *
4.0
40 A current sensitivity *
V1
V2
26.9
19.8
9.9
2.4
7.4
6.8
3.0
5.1
5.0 *
V1
V2
7.4
2.4
6.8
3.5
V1
V2
38.0
1.6
26.8
1.6
19.8
2.4
18.6
3.0
3.5
2.4
0.0
0.0
123
1
Breaker for Wiring *
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 seconds or less
1
Breaker for Wiring *
Breaker for Current Leakage
40 A
40 A 30 mA 0.1 seconds or less
Local switch (A)
Breaker for wiring
2
Capacity
Fuse
5
16
16
5
25
25
5
32
32
4
Sample chart
6000
600
60
10
1
0.1
0.01
1
2
3
Rated Tripping current (x)
Continue to the next page.
(NFB)
20
30
40
Sample
4
6
8
10
20
C