Installation and Operating Instruction for B.E.G. - Mini occupancy detector PD9-M-1C(-GH)-FC
1. Mounting preparation
Work on the mains supply may only
be carried out by qualified profes-
sionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrical
regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
5. Option: Remote control IR-PD-1C
B.E.G.
B.E.G.
B.E.G.
LUXOMAT
LUXOMAT
®
®
IR-PD-1C
PD3
LUXOMAT
®
500
400
200
100
20
HA
ON/OFF
PIR
CdS
Wall bracket for remote control
IR-PD-1C
An adhesive film for the surface of the IR-PD-1C is
included with the device. If required, this can be used
for any B.E.G. remote control with 27 keys.
6. Connections (at power supply)
S
N
R
L'
L
9. Explanation of the remote control button functions
9 a. In the initialisation period
12 h Light ON/OFF (party function)
Activated by "Light" - push button
Deactivated by "Reset"- push button (default)
Corridor function (see point 11 a)
Activated by "outside"- push button
Deactivate by "inside"- push button (default)
Forced shutdown (see point 11 c)
Activated by "sun" - push button
Deactivate by "moon"- push button (default)
9 b. In opened state
This push button opens the detector and the following
functions can then be programmed.
Attention: The detector is closed automatically:
• after every voltage recovery
• after 3 minutes
The state changes to "closed".
In the first 5 seconds, the white LED flashes every 0.5
seconds. During this time, sabotage protection can be
activated.
®
2. Installation LUXOMAT
®
PD9-M-1C-FC
The detector has been
≥28mm
designed and developed
specifically for installation
in suspended ceilings.
A circular opening of
diameter min. 28 mm
must be produced in the
ceiling.
Having connected the cables in accordance with
the regulations, connect the power supply via the
RJ11 plug. Therefore, open the power supply with
the help of the screws and close it afterwards.
After that, put the power supply through the open-
ing in the ceiling and mount the sensor onto the
ceiling according to figure.
7. Settings by remote control
Resetting when
open:
Deletes all values
set with the re-
mote control, light
OFF.
The device distinguishes between 2 procedures:
• Reading in with lighting switched on:
• Reading in with lighting switched off:
20
If the brightness has been modified, the switch-off
threshold is recalculated.
1000
Each time the push button is pressed, the device
increases the current switch-on value in increments of
+
20 lux for a current switch-on value of < 100 lux and
in increments of 50 lux for a current switch-on value
of > 100 lux.
Standard sensitivity for most applications
Reduced sensitivity for outdoor applications
PD9-M-1C(-GH)-FC
3. Hardware configuration
Position LED's s
LED 1 green
LED 2 red
LED 3 white
Self test cycle
After an initial 60-second self-test cycle, the
LUXOMAT
PD9-M-1C-FC is ready for operation.
®
LED function displays
(see
Unlocking device – Activation
of the programming mode
Daytime operation, detector only
activated by motion
or
Automatic reading in the current light
value as new luminance set point
or
Luminance set point for channel 1
to
1000
20
20 - 1000 Lux
Increase the current light level by
+
20 resp 50 Lux
Change between motion detector
PI R
and photo electric switch
CdS
Follow-up time channel 1 (light)
��
5
��
to
5 - 30 min. or impuls
���
min
���
Detection sensitivity reduced
or
or normal
Change between fully automatic
HA
and semi automatic mode (HA)
ON/OFF
Light ON/OFF
LED ON/OFF (by holding
down the push button)
Locking device – Exit programming
mode
t < 5 sec.
white LED flashes
Permanent protection against
sabotage
The switch-on value is determined automatically.
Determining the switch-on value:
1. Press the "eye" push button
2. Switch off the light (2 seconds later)
3. Read in the brightness
4. Switch-on value = Read brightness
When the push button is pressed, the current
brightness is specified as the switch-on value. The
switch-off value is determined automatically.
4. Putting into operation of the remote
control IR-PD-1C (optional)
Check Battery:
Open battery compartment
1 2 3
by pressing the plastic springs
together and removing the
battery-holder.
Caution: Settings with remote control supersede the
settings by potentiometers.
see point 19).
8. Key functions in closed state
t < 5 sec.
50
Lux
max
ON
��
OFF
���
When the pulse function is active, a pulse of 1 sec. is gener-
ated every 9 sec. If the pulse function is activated via remote
control, the pause between 2 pulses can be modified. After
activating the function via the "Pulse" push button, select the
desired time within 5 sec.:
��
5
= 9 sec.,
��
10
min
min
���
���
The "Test" push button can be used to set the LED ON/
OFF function. To do this, hold down the push button for
3 sec.
Please note that in the open state and in test mode, the
LED indicators are always ON.
Twilight switch function (CdS)
PI R
If the CdS function is active, the detector acts as a simple
CdS
twilight switch. Only the brightness can be set in this mode.
Movements are no longer indicated by the red LED.
Push button acknowledgement:
Each push of a button is indicated by lamp acknowledgement
and by the white LED.
"Light ON" status: OFF/ON (approx. 0.5 sec. each)
"Light OFF" status: ON/OFF (approx. 0.5 sec. each)
GB
Permanent protection against sabotage
This function blocks the unit perma-
nently. This operating mode can only be
activated during the period of 5 seconds
(white LED flash) after pressing the "Lock"
button. The procedure for leaving this
mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3. Switch of the current again
4. Apply current, wait for selftest
1500
Lux
cycle
5. Open detector
Light ON/OFF during the detection of
motion plus follow-up time; Activation
of the 12 h-ON/OFF-function by
holding down the push button
Activation/Deactivation of the test
function
Switches channel off and is immedi-
ately active again, exits all timers,
interruption of light measurement
Confirmation
Changes to „open" state
= 10 sec.,
��
15
= 15 sec.,
��
30
= 30 sec.
min
min
���
���

Advertisement

loading

Summary of Contents for B.E.G. LUXOMAT PD9-M-1C-FC

  • Page 1 After an initial 60-second self-test cycle, the the help of the screws and close it afterwards. location where there is least LUXOMAT PD9-M-1C-FC is ready for operation. ® daylight. After that, put the power supply through the open- LED function displays (see see point 19).
  • Page 2 If 110-240 V AC is applied at the slave input for longer than Motion detection Red flashes on each detected movement 10 sec., the light is switched on permanently. When the 110-240 PD9-M-1C-FC (Master) 92900 92901 V is removed, the light is switched off and automatic mode is...

This manual is also suitable for:

Pd9-m-1c-gh-fcPd9-s-dePd9-s-gh-de929009290592923 ... Show all