10. Switch-off threshold brightness
1. If the switch-on threshold has been modified by the potentiometer
or remote control, the switch-off threshold stored in the EEPROM
is deleted and is then recalculated on the next activation.
Determining the switch-off value
1. Switch on for 5 min. with dark and motion
2. Light OFF for 2 sec.
3. Internal calculation of the switch-off value
2. If the eye push button is pressed, the switch-off threshold is
recalculated. See also Remote control–> Eye section
3. Switch-off delay
If the determined switch-off threshold is exceeded during opera-
tion, the detector only switches off after a delay of approx.
15 minutes. This compensates for any brief fluctuations in the
brightness.
11 a. Behaviour of external push button/IR "Light"
The "Corridor" and "Light ON/OFF" functions are mutually
exclusive. If both are activated, the detector performs the corridor
function.
The behaviour when the push button is pressed is defined as
follows:
Corridor function activated
Light ON:
Push button pressed briefly: Light OFF -> Active after 5 sec.
Push button held down: Light OFF -> Active after 5 sec.
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: Light ON as long as motion + Lag time
11 b. Behaviour of external push button/IR "Light"
12 h Light ON/OFF activated
Light ON:
Push button pressed briefly: Light OFF -> Active after 5 sec.
Push button held down: 12 h OFF
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: 12 h ON
12 h Light ON/OFF deactivated
Light ON:
Push button pressed briefly: Light OFF as long as motion + Lag time
Push button held down: Light OFF as long as motion + Lag time
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: Light ON as long as motion + Lag time
11 c. Behaviour of external push button/IR
„Forced shutdown"
Forced shutdown active
Light OFF:
Light OFF: Push button pressed briefly: Light ON for approx. 30 min.,
then forced shutdown if the set brightness is still exceeded.
12. Other functions
Activation of light for 12 h via mains interruption
1. Interrupt current
2. Apply current for 2 to 5 sec.
3. Interrupt current again
4. Apply current
5. Detector is now ON for 12 h
Exiting sabotage
1. Interrupt current
2. Apply current for 30 to 60 sec.
3. Interrupt current again
4. Apply current
5. Detector is in simple closed state
110-240 V AC permanently at the slave input
If 110-240 V AC is applied at the slave input for longer than
10 sec., the light is switched on permanently. When the 110-240
V is removed, the light is switched off and automatic mode is
activated.
110-240 V AC for 1 - 3 sec. at push button connection S
If 110-240 V AC is applied for 1 - 3 sec. at push button connection
S, this is interpreted as a slave signal at slave connection R. This
ensures that the detector is compatible with previous versions.
13. Reset and default settings
1. Default settings
If the detector is not programmed, the factory setting is activated:
500 Lux and 10 min
2. Reset
After a reset in open state, all factory settings are activated.
14. Fully automatic and semi automatic mode
(see functions IR-PD-M-1C)
Fully automatic operation
In this operating mode, the lighting switches automatically on and off
for increased comfort, depending on presence and brightness.
- Channel 1 switches on in the event of motion if "dark" is detected.
Semi automatic operation
In this operating condition, in order to gain increased savings, the
lighting is energized only after being manually switched on.
Switch-off takes place automatically or manually.
The semi automatic mode basically behaves like the fully automatic
one. However, the difference is that switching-on must always be car-
ried out manually !
As many (NO-contact) buttons as desired can be wired in parallel on
the "S" button input (ON /OFF).
Triggering in semi automatic mode: If the detector switches off in semi
automatic mode (lag timer elapsed), the detector is switched on again
within 10 sec. by motion (despite semi-automatic mode).
15. Range of Coverage
1
walking towards
walking across
2
PD9-M-1C
seated
3
RJ
2.50 m
10,00 m
6,00 m
3
1
2
16. Exclude sources of interferences
PD9-M-1C
In case the sensing area of the LUXOMAT
PD9-M-1C-(GH)-FC is too large or areas are being covered that
should not be monitored, the range can be reduced or limited
through use of the enclosed masking clips.
19. LED function displays
LED function indicators after each mains recovery (60 sec. initialisation period)
Operating state
LED function indicators
Factory program
White, red and green flash in quick succession for 10 sec., then initialisation indicators, see
active
below
Double-locked
White and green shines for 5 sec. all 20 sec., afterwards initialising notificatian
Indicator
unprogrammed
Standard mode
Red flashes
12 h ON/OFF
Red and green flash
active
Corridor active
Red and white flash
12 h ON/OFF &
Red, green and white
corridor active
flash
CdS active
LED function indicators during operation
Process
LED function indicators
Motion detection
Red flashes on each detected movement
Semi automatic mode active
White is ON
Impulse mode active
Red and green flash one time all 4 sec.
Corridor active
White ON 1 sec. and OFF 4 sec.
Corridor and semi automatic
White ON 4 sec. and OFF 1 sec.
mode active
Too bright detected
Green flashes
Light measurement active
Green flashes once every 10 sec.
12 h ON/OFF function active
Red and green flash alternately
Duration ON active
Red flashes quickly
(by slave)
IR command
White flashes once
IR command "Open" and
White and green flash once slowly
sabotage active
17. Technical data PD9-Master-1C
HA
ON/OFF
Connection of sensor and power supply
by means of telephone plug R J11
Power supply: 110 - 240 VAC, 50/60 Hz
Power consumption: 0.5 W
Ambient temperature: -25°C – +50°C
Degree of protection/class: IP20 / II
Settings: by remote control
Light values: 20 - 1000 Lux
Extension of the detection area: with Slaves
Area of coverage: circular 360°
Range Ø H 2.50m/T=18°C:
seated 4.00m / tangential 10 m / radial 6 m
Recommended height for mounting 2 - 3 m
Light measurement: daylight and artificial light
• One channel to switch the lighting
Type of contact: NOC/with pretravel tungsten contact
Contact load: 2300 W cos ϕ=1 /
1150 VA cos ϕ= 0.5
Time-settings:
5 min. - 30 min. / Test with remote control
Dimensions:
PD9-M-1C-FC
PD9-M-1C-GH-FC H 40 x Ø 36 mm
Power supply
Visible part when built into ceiling:
PD9-M-1C-FC
PD9-M-1C-GH
PD9-M-1C-GH-FC H 24 x Ø 36 mm
RJ
Technical data PD9-Slave
Electrical data same as above, but just one channel
for signaling motion detection.
Declaration of Conformity: The product complies
with the low voltage recommendation 2006/95/EC
and the EMV recommendation 2004/108/EC.
18. Wiring diagram
Standard mode master 1-channel occupancy
detectors with R and S terminal
L
N
PD9-M-1C-GH
®

optional: T1 = NO - Push button for semi automatic;
Extension of the detection area with Slave-devices
Indicator
Indicator also when forced shutdown is
programmed
activated
Red flashes quickly
Every 5 sec., 4 x white, red and green in
quick succession
Red and green flash quickly
Every 5 sec., 4 x white, red and green in
quick succession
Red and white flash
Every 5 sec., 4 x white, red and green in
quickly
quick succession
Red, green and white flash
Every 5 sec., 4 x white, red and green in
quickly
quick succession
Red and white flash
Then no red LED for motion detection
20. Article / Part nr. / Accessory
Typ
PD9-M-1C-FC (Master)
PD9-S-DE (Slave)
PD9-M-1C-GH-FC
PD9-S-GH-DE (Slave)
LUXOMAT
IR-PD-1C (
IR-PD-Mini
Accessory
Cover ring for PD9
Cover ring for PD9
Cover ring for PD9
Blind GH
H 28 x Ø 36 mm
L165 x W 24 x H 24 mm
H 12 x Ø 36 mm
T1
E1
S
N
L
L΄ ΄ ΄ ΄
R
R
N
L
C1


RAL9010
RAL9006
92900
92901
92905
92906
92923
92925
92928
92929
Remote control:
®
)
92520
incl. wall bracket
92159
:
white
92238
silver
92237
anthracite
92235
white
33207

Advertisement

loading

This manual is also suitable for:

Pd9-m-1c-gh-fcPd9-s-dePd9-s-gh-de929009290592923 ... Show all