2. Installing a Terminal Cap on a
Chase Enclosed Chimney.
Construct a chase of desired materials maintaining a
minimum 2" air space around the chimney.
NEVER INSTALL A SINGLE WALL
SLIP SECTION OR SMOKE-PIPE IN
A CHASE STRUCTURE. THE
HIGHER TEMPERATURE OF THIS
SINGLE WALL PIPE MAY RADIATE
SUFFICIENT HEAT TO COM-
BUSTIBLE CHASE CONSTRUC-
TION MATERIALS TO CAUSE A
For installations utilizing a telescoping round terminal
cap (TR342), the uppermost chimney section must be
below the top of the chase top, but not more than
14-1/2" below the top of the chase top flashing collar.
For installations utilizing a square terminal cap
(ST375), the last chimney section must not be more
than 4-3/4" below the chase top. See Figure 24.
When installing a TS345 Square Termination, the
uppermost chimney section must not be more than
3" below the chase top. See Figure 24.
Attach the chase top (CT35) to the top of the chase.
Install the terminal cap, using the instructions provid-
ed with it.
Installing a Terminal Cap
3-00
WARNING!
FIRE.
Figure 24
RHW-44 WOODBURNING FIREPLACE
H. OPERATING
INSTRUCTIONS
SAVE AND PASS THESE OPERATING
INSTRUCTIONS AND THE
INSTALLATION INSTRUCTIONS TO
SUBSEQUENT OWNERS. THE
INFORMATION PROVIDED IS
INTENDED TO NOTIFY AND WARN
THEM ABOUT MAKING UNSAFE
FUTURE MODIFICATIONS SUCH AS
THE ADDITION OF SHELVES OR THE
USE OF UNAUTHORIZED PARTS AND
This fireplace is intended to operate as a supple-
mental heat source for a single room. It is not
designed to function as a primary heat source for
a structure.
Fireplaces, as well as other woodburning appliances,
have been used safely for many years. It has been
our experience that most problems are caused by the
improper installation and operation of the unit. Make
certain installation and operation of the fireplace sys-
tem is in accordance with these instructions.
It is extremely important that the fire be supervised
whenever the fireplace is in use. It is also recom-
mended that an annual inspection be performed on
the fireplace system to determine if the flue system
needs to be cleaned, or as in the case of any appli-
ance, if minor repairs are required to maintain the
system in top operating condition.
INTENDED USAGE.
intended for use with either solid fuel (firewood) or a
decorative gas appliance that has been tested and
listed to the Standard for Decorative Gas Appliances
for Installation in Vented Fireplaces, ANSI Z21.60.
When operating your fireplace, the flue damper
must be in the open position.
This fireplace was not tested and listed for use with
an unvented gas log heater. Do not install an unvent-
ed gas log heater in this fireplace and operate it with
the flue damper in the closed position unless the
unvented gas log set has been specifically tested and
listed for use in this fireplace by Underwriters
Laboratories Inc. Use of an unvented gas log heater
in this factory-built fireplace may create a fire hazard
that can result in a structure fire.
20
NOTICE:
REPAIRS.
This factory-build fireplace is
33147A