READy MTU
1. The LED starts blinking 3 times every 5 seconds.
NOTE: Finish all cable connections before activating
READy MTU.
2. When the LED blinks 1 time every 5 seconds, everything
is OK.
READy MTU is reading the encoded output and sending
data via AMI.
The LED automatically stops blinking after 5 minutes. No further configuration is needed.
The configuration of a preconfigured MTU can at all times be read and changed by following the steps in section 9.5

Reconfiguration.

8.3.2 Configuration of default configured MTU
A default configured MTU requires configuration using READy App.
The reading on the encoded output must match the imported meter ID/serial number in READy Manager. If the
IDs do not match, you can overwrite the encoded output reading to ensure data flows to the correct meter.
1. Sync READy Manager and READy App before
proceeding to step 2.
2. Activate READy MTU by pointing a magnet at the
designated spot.
3. The LED starts blinking.
Kamstrup A/S • 55122662_C1_US_06.2020
Installation & operation guide
15