Circuit diagrams
14.3 Typical circuits
Typical circuits for 3SK1 Standard solid-state basic units or 3SK1 Advanced basic units
Table 14-8
Typical circuit 8: EMERGENCY STOP two-channel, with cross-circuit detection, with monitored start
Table 14-9
Typical circuit 9: Two-channel, with cross-circuit detection, with autostart
216
•
Monitored start
•
With cross-circuit detection
•
1 x two-channel
•
Sensor: 2 NC contacts
•
3SK1112 Standard solid-state and
3SK112 / 3SK122 Advanced
DIP switch
1
2
ON
ON
Right
Right
Up to PL in accordance with ISO 13849-1 e
Up to Safety Integrity Level (SILCL) to
IEC 62061
•
Autostart
•
With cross-circuit detection
•
1 x two-channel
•
Sensor: 2 NC contacts
•
3SK1112 Standard solid-state and
3SK112 / 3SK122 Advanced
DIP switch
1
2
OFF
ON
Left
Right
Up to PL in accordance with ISO 13849-1 e
Up to Safety Integrity Level (SILCL) to
IEC 62061
SIRIUS 3SK1 Safety Relays and 3RQ1 Positively-Driven Coupling Relays
Equipment Manual, 05/2021, A5E02526190021A/RS-AE/005
3
4
ON
—
Right
3
3
4
ON
—
Right
3