NC Curves

38VMA072RDS5-1
Standard
60Hz
Low noise mode
60Hz
38VMA072RDS6-1
Standard
60Hz
Low noise mode
60Hz
NOTE: When silent mode is set, the unit's capacity is limited. The unit will automatically exit silent mode if high pressure exceeds 522
psi. The unit will automatically return to silent mode once high side pressure falls below 479 psi.
Fig. 23 —38VMA072RDS5-1
Table 30 —38VMA072RDS5-1
63
125
250
66.9
66.3
58.5
55.6
51.7
52.4
Fig. 24 —38VMA072RDS6-1
Table 31 —38VMA072RDS6-1
63
125
250
68.5
65.2
57.8
56.3
56.0
51.3
39
500
1000
2000
57.5
50.7
46.3
51.3
45.8
42.0
500
1000
2000
56.4
51.1
45.0
50.0
44.2
42.3
4000
8000
dB(A)
42.1
36.7
58.8
41.6
37.1
52.4
4000
8000
dB(A)
39.0
36.8
57.7
36.0
36.3
51.5