Indoor Unit Electrical Connections - LG LV181HV4 Installation Manual

Single zone vertical air handling unit 18,000 - 48,000 btu/h
Table of Contents

Advertisement

External Static Pressure Setting Values (NK frame)
Figure 70: ESP Setting Values (NK frame).
IDU External Static Pressure Setting Values
Table 18: Vertical Air Handling Unit Indoor Unit External Static Pressure and Air Flow Tables.
Static Pressure (in. wg)
Model No. / Nominal
Capacity of System
Airflow Rate / CFM
(Btu/h)
High
LVN420HV / 42,000
Mid
Low
High
Mid
LVN480HV / 48,000
Low
1 Unless otherwise noted, vertical air handling units are UL listed up to 0.5 in. wg total static pressure, including coil, case, duct work pressure drop, air filter, and largest kW size heater.
Internal static pressure includes coil and case only.
* Airflow rate (CFM) decreases by 3% per 0.1 in. wg.
Factory default status is 0.3 in wg.
Factory default is high static pressure.
• If the ESP is set incorrectly, the air conditioning may malfunction.
• To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other than the values
listed in the table will not provide the desired combination.
ELECTRICAL SYSTEM INSTALLATION
0.1
0.2
1,260
70
77
1,100
65
71
1,000
61
67
1,400
77
82
1,260
70
77
1,000
61
67
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
External Static Pressure Setting Values
0.3
0.4
0.5
0.6
Setting Value (in. WG)
83
90
96
98
79
86
92
96
75
82
88
94
87
94
100
102
83
90
96
98
75
82
88
94
0.7
0.8
0.9
1
1
104
108
116*
_
102
106
114
_
100
104
112
116*
106
110
116*
_
104
108
114
116*
100
104
112
116*
51