LG LV181HV4 Installation Manual page 34

Single zone vertical air handling unit 18,000 - 48,000 btu/h
Table of Contents

Advertisement

REFRIGERANT SYSTEM ENGINEERING
Pipe Sleeves at Penetrations
LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an
appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the
sleeve. Use 4"+ curved sheet metal saddles between the bottom surface of the pipe and the bottom surface of the penetration.
Figure 37: Pipe Sleeve Options.
Diameter of penetrations shall be determined by pipe diameter plus the thickness of the insulation.
Underground Refrigerant Piping
Refrigerant pipe installed underground must be routed inside a vapor tight protective
sleeve to prevent insulation deterioration and water infiltration. Refrigerant pipe in-
stalled inside underground casing must be continuous without any joints. Underground
refrigerant pipe must be located at a level below the frost line.
Table 13: Utility Conduit Sizes.
Liquid Pipe
1
1/2 (2.0
2,5
1/4 (1.0)
4
3
3/8 (1-1/8)
4
3
1/2 (1-1/2)
5
4
5/8 (1-5/8)
5
4
3/4 (1-3/4)
5
4
OD pipe diameter in inches; Values in parenthesis () indicate OD of pipe with insulation jacket.
1
Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness may
2
vary based on surrounding ambient conditions and must be calculated and specified by the design
engineer.
Insulation thickness (value in parenthesis) = 3/8 inch.
3
Insulation thickness (value in parenthesis) = 1 inch.
4
Insulation thickness (value in parenthesis) = 3/4 inch.
5
34 | INTRODUCTION
Vapor Pipe
1
)
5/8 (2-1/8
)
3/4 (2-1/4
2,5
4
4
4
5
5
5
5
5
5
5
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 38: Typical Arrangement of Refrigerant Pipe
and Cable(s) in a Utility Conduit.
)
2,5
Table 14: Heat Pump Unit Refrigerant Pipe Connections (All Brazed).
Model
LUU189HV, LUU249HV, LUU369HV,
LUU428HV, LUU488HV
Provide expansion joints in long pipe segments and place in an accessi-
ble conduit box for inspection. Use galvanized curved sheet metal sad-
dles at all mounting points. Pipe must be allowed to move freely linearly.
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve
Insulation
Material
Min. 14 Gauge
Power/Communication
Cable
Liquid Conn.
Vapor Conn.
(inches)
(inches)
3/8
5/8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lv241hv4Lv361hv4Lv420hvLv480hv

Table of Contents