External Static Pressure Setting Values - LG LV181HV4 Installation Manual

Single zone vertical air handling unit 18,000 - 48,000 btu/h
Table of Contents

Advertisement

ELECTRICAL SYSTEM INSTALLATION

External Static Pressure Setting Values

External Static Pressure (ESP) Default Settings (NJ frame)
Table 17: ESP Setting Values (NJ frame).
Model Number
High
LVN181HV4
640
LVN241HV4
710
LVN361HV4
990
*Installer settings available to change the CFM to 10% above or 10% below the values mentioned in the above table.
How to Enter Installer Setting Mode
Follow this procedure to enter installer setting mode and set the target air volume as desired.
50
Air Volume*
Medium
Low
580
480
640
480
880
800
1. Press
button and
setting mode.
2. When entering installer setting mode, fuction code is displayed on the LCD screen.
3. Press
button to select function code 64 (target air volume).
4. Press
buttons to change value as desired (00 = Default; 01 = +10%; 02 = -10%).
5. Press
button to set value.
6. Press
button and
setting mode.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
button simultaneously for 3 seconds to enter the installer
button simultaneously for 3 seconds to exit installer

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lv241hv4Lv361hv4Lv420hvLv480hv

Table of Contents